E6581741
- 8 -
Title
Communi
cation No.
Function Description
Factory
setting
c021
C021
Scanner output 1 address (*3)
0: -
1:
fd01
(Status information 1)
2:
fd00
(Output frequency, 0.01Hz)
3:
fd03
(Output current, 0.01%)
4:
fd05
(Output voltage, 0.01%)
5:
fc91
(Alarm information)
6:
fd22
(PID feedback value, 0.01Hz)
7:
fd06
(Input terminal board status)
8:
fd07
(Output terminal status)
9:
fe36
(VIB input, 0.01%)
10:
fe35
(VIA input, 0.01%)
11:
fe37
(VIC input, 0.01%)
12:
fd04
(Input voltage (DC detection), 0.01%)
13:
fd16
(Estimated speed 0.01Hz)
14:
fd18
(Torque, 0.01%)
15: -
16: -
17: -
18: -
19:
f880
(Free notes)
20:
fd29
(Input power, 0.01kW)
21:
fd30
(Output power, 0.01kW)
22:
fe14
(Cumulative operation time, hour)
23:
fe40
(FM terminal output monitor, 0.01%)
24: -
25:
fd20
(Torque current, 0.01%)
26:
fd23
(Motor overload factor, 0.01%)
27:
fd24
(Drive overload factor, 0.01%)
28:
fd25
(PBR overload factor, %)
29:
fd26
(Motor load factor, %)
30:
fd27
(Drive load factor, %)
31:
fe56
(Pulse train input, pps)
32:
fe70
(Drive rated current, 0.1A)
33:
fe76
(Input Watt-hour, 0.1kWh 10
f749
)
34:
fe77
(Output Watt-hour, 0.1kWh 10
f749
)
35:
fd83
(IGBT temperature, degree C)
1
c022
C022
Scanner output 2 address (*3)
0-35 (Same as
c021
)
2
c023
C023
Scanner output 3 address (*3)
0-35 (Same as
c021
)
0
c024
C024
Scanner output 4 address (*3)
0-35 (Same as
c021
)
0
c025
C025
Scanner output 5 address (*3)
0-35 (Same as
c021
)
0
c026
C026
Scanner output 6 address (*3)
0-35 (Same as
c021
)
0
c081-
c096
C081-
C096
Device Name 1-16 (*4)
16 characters
The device name is required if the card uses
DHCP to obtain its IP Address.
Refer to " 3.2.1 Device name (c081-c096) for the
details.
0,0,0,0,
0,0,0,0
c100
C100
Communication error
detection delay time
0.0 - 100.0 sec.
0.0
c101
C101
Inverter operation at the
communication loss action
0: Stop and controlled by
cmod
,
fmod
1: Operation continue
2: Deceleration stop
3: Coast stop
4: Network error stop (
err8
trip)
5: Preset speed operation (by
c102
setting)
4
c102
C102
Preset speed operation
selection
0: None
1 to 15: Preset speed
0
c103
C103
Communication time-out
condition selection
0: Disconnection detection
1: When communication mode enable (Both
cmod
and
fmod
are set CANopen or
communication option) only
2: 1 + Driving operation
0
(*3): This parameter is effective by reset. Please reset (power supply reset or
f899
=
1
) after changing a set point.
(*4): (
V[R
) does not work for this parameter.
Содержание EtherNet/IP Modbus IPE002Z
Страница 57: ...E6581741 56 Select the Module as below Select revision of drive Put in Name and IP address and press OK button ...
Страница 61: ...E6581741 60 Select the Download Once again select the Download ...
Страница 64: ...E6581741 63 ...
Страница 83: ...E6581741 82 13 3 Drive monitor Main menu Monitoring The state of the drive can be confirmed on this page ...
Страница 85: ...E6581741 84 Input the write value to popup window ...
Страница 89: ...E6581741 88 13 9 TCP IP statistics Main menu Diagnostics You can check TCP IP status on this page 88E ...