E6581741
- 47 -
5.1.5.
Instance 100: Native drive output
Instance 100 mapping
Byte
Bit 7
Bit 6
Bit 5
Bit 4 Bit
3 Bit
2 Bit
1 Bit
0
0
DC braking
ACC1/
ACC2
PI off
THR2
Preset
Speed4
Preset
Speed3
Preset
Speed2
Preset
Speed1
1
Net Ctrl*
Net Ref *
Reset trip
Emergency
stop
Free run
(ST)
Run/stop
Forward/
Reverse
Jog
2
Drive Reference Speed Hz (Low byte) **
3
Drive Reference Speed Hz (High byte) **
* Bit 6 and 7 of the instance 100 byte 1 are defined as follows.
Bit 7 (Net Ctrl)................. When “1” is set, all commands of byte 0 and 1 are enabled. When “0” is set,
each command is according to setup of the parameter
cmod
.
Bit 6 (Net Ref)................. When “1” is set, bytes 2 and 3 are enabled. When “0” is set, Drive Reference
Speed is according to setup of the parameter
fmod
.
**
Drive Reference Speed
is set up by 0.01Hz unit and the hexadecimal number.
For example, when "Frequency reference" is set up to 60Hz, since the minimum unit is 0.01Hz,
60 / 0.01 = 6000 = 1770H
5.1.6.
Instance 150: Native drive input
Instance 150 mapping
Byte
Bit 7
Bit 6
Bit 5
Bit 4 Bit
3 Bit
2 Bit
1 Bit
0
0
DC braking
ACC2
PI
THR 2
(
vf2
+
th2
)
-
ALARM
(
fc91
)
EMG FL
1
-
READY
without
ST/RUN
READY
with
ST/ RUN
Emergency
stop
Free run
(ST)
Run/Stop
Forward /
Reverse
Jog
2
Drive Actual Speed Hz (Low byte)
3
Drive Actual Speed Hz (High byte)
Содержание EtherNet/IP Modbus IPE002Z
Страница 57: ...E6581741 56 Select the Module as below Select revision of drive Put in Name and IP address and press OK button ...
Страница 61: ...E6581741 60 Select the Download Once again select the Download ...
Страница 64: ...E6581741 63 ...
Страница 83: ...E6581741 82 13 3 Drive monitor Main menu Monitoring The state of the drive can be confirmed on this page ...
Страница 85: ...E6581741 84 Input the write value to popup window ...
Страница 89: ...E6581741 88 13 9 TCP IP statistics Main menu Diagnostics You can check TCP IP status on this page 88E ...