58
4200FA XT 80kVA Installation and Operation Manual
Installation Planning Guide for 80kVA UPS
Standard Systems: 208/120V Wye, 208/380/480/600V Delta Input, 208/120V Output
For Maximum cable sizes, see Note 7.
General Mechanical Information
UPS kVA/ kW Rating
Vin // Vout
Dimensions
(W x D x H)
Weight
Lbs.
Approximate Thermal Load
at Rated Output
Inches
kBTU’s / Hr.
80 kVA / 64 kW
208/120 Vin // 208/120
Vout
44 x 31 x 74
2100
29.8
80 kVA / 64 kW
208 Vin // 208/120
Vout
44 x 31 x 74
2300
34.4
80 kVA / 64 kW
380 Vin // 208/120
Vout
44 x 31 x 74
2300
34.4
80 kVA / 64 kW
480 Vin // 208/12
Vout
0
44 x 31 x 74
2300
34.4
80 kVA / 64 kW
600 Vin // 208/12
Vout
0
44 x 31 x 74
2300
34.4
Primary AC Input
Maximum Input Power Demand
Suggested
External Feeder
Breaker
Suggested Minimum Feeder Wire
Size Per Phase / Neutral
Suggested Maximum
Feeder Length For Min. Wire
Size in Steel Conduit
Vin
PF
Amps – Nom. (Max)
Amps
AWG or kcmil at 75º C Temp. Rating
Feet
208/120 Wye >0.98
208 (224)
300 A
(1)x500 kcmil /(1) x 500 kcmil
480
208 Delta
>0.98
208 (224)
300 A
(1)x300 kcmil
480
380 Delta
>0.98
114 (123)
175 A
(1) x 2/0
480
480 Delta
>0.98
90 (97)
120 A
(1) x #2 AWG
480
600 Delta
>0.98
72 (78)
100 A
(1) x #3 AWG
480
Optional Alternate AC Input – All 80 kVA Models (208/120V 3-Phase / 4-Wire)
Maximum Input Power Demand
Suggested
External Feeder
Breaker
Suggested Minimum Feeder Wire
Size Per Phase / Neutral
Suggested Maximum
Feeder Length For Min. Wire
Size in Steel Conduit
Vin
PF
Amps – Nom. (Max)
Amps
AWG or kcmil at 75º C Temp. Rating
Feet
208/120 Wye >0.98
208 (224)
300 A
(1)x500 kcmil /(1) x 500 kcmil
480
Battery Input (288VDC Nominal)
Battery Capacity Required
for Full Load Output
Maximum Discharge
at Full Load Output
Suggested External
Feeder Breaker
Suggested Minimum Feeder
Wire Size
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
kWB
Amps DC
Amps
AWG or kcmil at 75º C Temp. Rating
Feet
80
77
335
350 A
(1) X 400 kcmil
or (2) x 2/0
70
AC Output (208/120V 3-Phase / 4-Wire)
Rated Output Power Demand
Suggested
External Feeder
Breaker
Suggested Minimum Feeder Wire Size
Per Phase / Neutral
Suggested Maximum
Feeder Length For Min. Wire
Size in Steel Conduit
Vout
PF
Amps – Nom. (Max)
Amps
AWG or kcmil at 75º C Temp. Rating
Feet
208/120 Wye
0.8
222
300 A
(1) x 500 kcmil /(1) x 500 kcmil
480