4200FA XT 80kVA Installation and Operation Manual
5
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions
that should be followed during the
installation, operation, and maintenance of the UPS and its batteries. Turn off, lockout, and tagout all
power sources before proceeding to connect the power wiring to the equipment or when performing
maintenance. Hardwire type UPS units are not equipped with an over-current protection device nor an
output disconnect for the AC output. Therefore, a circuit breaker should be provided by the user
between the UPS output and the load input. This device should be rated as follows:
Device Type
80 kVA
Rated Output
208/120 VAC
Device Rating
240 V, 300 A
The maximum ambient temperature in which the UPS unit should be operated is
40°C (104°F)
.
The nominal battery voltage is 288VDC.
Only a qualified TOSHIBA Representative who is knowledgeable in batteries and the required
precautions should only perform battery servicing. Keep unauthorized personnel away from batteries. To
arrange for battery replacement, contact TOSHIBA for service.
Qualified Personnel ONLY
A Qualified Person is one that has the skills and knowledge relating to the construction, installation,
operation, and maintenance of this electrical equipment and has received safety training on the hazards
involved (Refer to the latest edition of NFPA 70E for additional safety requirements).
Qualified Personnel Shall:
1) Have carefully read the entire operation manual.
2) Be trained and authorized to safely energize, de-energize, ground, lockout/tagout circuits and
equipment, and clear faults in accordance with established safety practices.
3) Be trained in the proper care and use of protective equipment such as safety shoes, rubber gloves,
hard hats, safety glasses, face shields, flash clothing, etc., in accordance with established safety
practices.
4) Be trained in rendering first aid.
5) Be knowledgeable of batteries and the required precautions.
For further information of workplace safety visit www.osha.gov.
Refer to the Battery System Manual when scheduling battery maintenance or battery replacement.
DANGER
Misuse of this equipment could result in injury and equipment damage.
In no event will TOSHIBA Corporation be responsible or liable for
indirect, or consequential damage or injury that may result from the misuse of this equipment.
CAUTION
Do not dispose of the batteries in a fire. The batteries may
explode.
CAUTION
Do not open or mutilate the batteries. Released electrolyte is toxic and
harmful to the eyes and skin.