48
4200FA XT 80kVA Installation and Operation Manual
6.15.5 Serial Com Station Address
Press the MENU key to access the menu data screens. Press the Down arrow key to access
the Run/Switch select screen.
SER COM STATION ADDR
STATION ADDRESS: 31H
>*F1: DATA SET MODE
>
∆
/
∇
: PRV/NEXT SCREEN
Press the F1 key to display the following active adjustment screen:
SER COM STATION ADDR
STATION ADDRESS: 31H
>∆
/
∇
: CHANGE DATA
>ENTER: ACCEPT CHANGE
6.15.6 Output Voltage Adjustment
While operating in the AC Input mode, press the MENU key for 4 seconds or more to display
the output voltage adjustment screen:
OUTPUT VOLT. ADJUST
OUTPUT VOLTAGE =###%
>F1: DATA SET MODE
>
∆
/
∇
: PRV/NEXT SCREEN
Press the F1 key to display the following active adjustment screen:
OUTPUT VOLT. ADJUST
REFERENCE ADJUST: ##
>∆
/
∇
: CHANGE DATA
>ENTER: ACCEPT CHANGE
The fields marked
##
will show the numerical value of the allowable voltage adjustment
parameter values. Press the Up/Down arrow keys to adjust the setting ±5 volts. This results
in a ±2 % change in the output voltage.
Attempts to adjust this setting while the inverter is not running will result in the following error
message:
OUTPUT VOLT. ADJUST
ADJUST PROHIBITED
DATA CANNOT CHANGE
>
∆
/
∇
: PRV/NEXT SCREEN