4200FA XT 80kVA Installation and Operation Manual
15
4.1.2
Power Connection Cable Routing
1) Use separate metal conduits for routing the input power, output power, battery, and
control circuits.
2) A separate ground cable should be run inside of the conduit with the input power, output
power, and control circuits.
3) Always ground the unit to prevent electrical shock and to help reduce electrical noise.
4) Follow wire size and tightening torque recommendations provided in this manual.
CAUTION
THE METAL OF A CONDUIT IS NOT AN ACCEPTABLE
GROUND
Single Input UPS with input transformer. Shown with bottom cable entry
configuration.