4200FA XT 80kVA Installation and Operation Manual
47
6.15.3 Settings for Display Duration
The LCD display is designed to switch off after a user-set period of inactivity. To set the
duration of inactivity allowed, press the MENU key to access the menu data screens. Press
the Down arrow key to scroll to the Display Duration screen. The following system message
is displayed:
DISPLAY DURATION SET
<3 MIN> 30 MIN
>F1: DATA SET MODE
>
∆
/
∇:
PRV/NEXT SCREEN
Press the F1 key to adjust the LCD-Idle mode setting:
DISPLAY DURATION SET
<3 MIN> 30 MIN
>
∆
/
∇
: CHANGE DATA
>ENTER:ACCEPT CHANGE
Press the Up/Down arrow keys to toggle from 3 MIN to 30 MIN. Press the ENTER key to
save the selection or press the MENU key to exit to the main menu and discard the change.
Under any of the following conditions the LCD will remain on continuously without regard to
the Display Duration setting.
1) The UPS has received an emergency-off command.
2) The UPS is in battery discharge mode.
3) A fault has been detected in the main unit.
4) The UPS is in an overload condition.
6.15.4 Run Switch Select
Press the MENU key to access the menu data screens. Press the Down arrow key to scroll to
the Run Switch Select screen.
RUN SWITCH SELECT
<LOCAL> REMOTE
>*F1: DATA SET MODE
>
∆
/
∇
: PRV/NEXT SCREEN
Press the F1 key to display the following active adjustment screen:
RUN SWITCH SELECT
<LOCAL> REMOTE
>
∆
/
∇
: CHANGE DATA
>ENTER:ACCEPT CHANGE
Press the Up/Down arrow keys to toggle from RUN to SWITCH. Press the ENTER key to
save the selection or press the MENU key to exit to the main menu and discard the change
(Remote S/U option required). This function is available in the Bypass mode only.