Heater Start-Up Procedure (continued)
Perform the Start-Up
Automatic Detection
Five seconds after the diagnostic tool has been connected to the heater using the adapter cable, the automatic detection
starts to determine the type of heater to which the diagnostic unit is connected.
NOTE: If the automatic detection was successful, if necessary, the heater is briefly started and then switches off
again.
• Display until the automatic detection is completed.
• Heater Icon will display when heater has been detected.
Confirm flashing symbol with OK key.
Possible Displays:
• If no errors/faults exist go to Heater Start-up.
• If errors/faults exist go to Clearing Faults.
• Communication error. Go to Unable to Perform the Diagnosis
Содержание TriPac Envidia
Страница 2: ......
Страница 11: ...9 Battery Box Dimensions Figure 1 Battery Box Dimensions...
Страница 12: ...10 Battery Box Dimensions continued Figure 2 Battery Box Dimensions continued...
Страница 13: ...11 Evaporator Control Box Dimensions Figure 3 Evaporator Control Box Dimensions...
Страница 14: ...12 Condenser with Receiver Drier Dimensions Figure 4 Condenser with Receiver Drier Dimensions...
Страница 15: ...13 HMI Dimensions Figure 5 HMI Dimensions...
Страница 16: ...14 1000 Watt Power Inverter Dimensions Option Figure 6 1000 Watt Power Inverter Dimensions...
Страница 17: ...15 AC DC Shore Power Converter Dimensions Option Figure 7 AC DC Shore Power Converter Dimensions...
Страница 18: ...16 D2 D4 Heater Dimensions Option Figure 8 Heater Dimension...
Страница 19: ...17 BLANK PAGE...
Страница 21: ...19 Typical Component Locations Figure 9 Typical Component Locations...
Страница 45: ...43 A C Duct Installation continued FLUSH MOUNTED EVAPORATOR Figure 21 A C Duct locations...
Страница 76: ......
Страница 77: ......
Страница 78: ......
Страница 79: ......