Tips for a Successful Installation (continued)
•
Protective covers or sleeves (installer supplied) for the refrigeration hoses may be required depending on the
installation.
•
Always install the condenser’s receiver drier so refrigerant flow is in the direction indicated by the arrow.
•
Thermo King Evacuation Station (204-725) and Evacuation Station Operation and Field Application Instructions
(TK-40612) are recommended.
•
The oil in the evacuation station vacuum pump should be changed after each use.
•
The A/C system must be leak free. Check for leaks by using an electronic leak detector.
•
The A/C system will be charged with 2.0 lbs. of R134a refrigerant. NOTE: Accuracy is important. Over or under
charge by 3 ounces will reduce cooling capacity.
ELECTRICAL WIRING AND HMI CONTROLLER INSTALLATION
•
Electrical wiring should be installed and routed in such a way as to allow for vibration and movement of
the cab. THEY SHOULD NEVER BE STRETCHED TIGHT!
•
Always keep electrical wiring from rubbing or chafing against sharp metal objects, rotating components or hot objects.
•
All electrical wiring should be neatly routed and secured with band wraps or clamps.
•
Do note route or bundle 110Vac wires together with 12Vdc wires.
•
Do not route electrical wires, harness or battery cables together with fuel lines.
•
Excess length of battery cables should be cut off to reduce voltage drop.
•
Superlube (203-524) or equivalent should be applied to all electrical connections.
•
All main power and ground accessory connections must be installed directly on top of the tractor’s battery terminal
posts and tightened securely. DO NOT INSTALL UNDER OEM BATTERY CABLES!
Содержание TriPac Envidia
Страница 2: ......
Страница 11: ...9 Battery Box Dimensions Figure 1 Battery Box Dimensions...
Страница 12: ...10 Battery Box Dimensions continued Figure 2 Battery Box Dimensions continued...
Страница 13: ...11 Evaporator Control Box Dimensions Figure 3 Evaporator Control Box Dimensions...
Страница 14: ...12 Condenser with Receiver Drier Dimensions Figure 4 Condenser with Receiver Drier Dimensions...
Страница 15: ...13 HMI Dimensions Figure 5 HMI Dimensions...
Страница 16: ...14 1000 Watt Power Inverter Dimensions Option Figure 6 1000 Watt Power Inverter Dimensions...
Страница 17: ...15 AC DC Shore Power Converter Dimensions Option Figure 7 AC DC Shore Power Converter Dimensions...
Страница 18: ...16 D2 D4 Heater Dimensions Option Figure 8 Heater Dimension...
Страница 19: ...17 BLANK PAGE...
Страница 21: ...19 Typical Component Locations Figure 9 Typical Component Locations...
Страница 45: ...43 A C Duct Installation continued FLUSH MOUNTED EVAPORATOR Figure 21 A C Duct locations...
Страница 76: ......
Страница 77: ......
Страница 78: ......
Страница 79: ......