Heat Pump Manual
57
TECHNICAL DATA
–
20kW HEAT RECOVERY COIL
TECHNICAL DATA – FAN COIL UNIT
Model
HP20W3
ELECTRICAL DATA
Power Supply
415V 3 Phase – 50 Hz
Full Load Amps
A/ Ph
3.2
Fans
2 x 450mm
Air flow
Vertical discharge
Fan wiring
Star
Water connections
4 off
1 ” connection with motorized ball
isolation
Pressure drop across the coil
Pascals
90
Rated air flow
M
3
/h
10000
Sound at 5m
dB
66
Heat absorption 8/12°C cross the coil
kW
17
Heat rejection 50/45°C across the coil
kW
20
Coil construction
Copper tube – ½” – with aluminum
fins – Nano coated
-
Nano Coating on the coil fins is a glass/ silicon based coating which is super hydrophobic
that repels water and keeps coil dry.
-
Unit I supplied with electrical junction box for wiring connection.