Heat Pump Manual
28
INSTALLATION
Multiple Heat pump Installations
Aqua Coolers heat pump can be installed in multiple installations for redundancy or to allow
scaling
– up to 8 heat pumps can be installed together.
If the master heat pump loses power, develops a fault or the control wire between the heat
pumps is interrupted then all other heat pumps will keep operating on their internal
temperature controls.
If one of the slave heat pumps loses power or develops a fault then the master will move
along the line and turn the next one on.
One of the heat pumps will have to be designated the master and the other heat pumps will
need to be designated the slaves. This can be done in the programming. On the controller
use the up and down keys to scroll to the PARAMETERS MENU and press OK
– scroll to the
SYSTEM sub menu and scroll to MASTER/SLAVE option. The heat pump will be supplied as
MASTER being the default so any other heat pumps will need to be programmed to be the
slaves.
The wiring diagram will show how the units will need to be wired together and the electrical
box will have marked terminals. The unit will be supplied with 5 metres of 3 core shielded
cable. It is important that this cable is used to wire the units together and it is important that
the unit is wired together as shown above with the wire from the terminals matching up.
Содержание THW100
Страница 17: ...Heat Pump Manual 17 DIMENSIONS THW30 and THW40 THW50 and THW60 ...
Страница 18: ...Heat Pump Manual 18 DIMENSIONS THW80 THW100 AND THW130 ...
Страница 19: ...Heat Pump Manual 19 DIMENSIONS THWW20 to THWW40 Water to Water THWW50 THWW60 and THWW80 Water to Water ...
Страница 58: ...Heat Pump Manual 58 WIRING DIAGRAM 20kW HEAT RECOVERY COIL ...