Heat Pump Manual
27
INSTALLATION
The SNMP, BACnet IP and Modbus TCP interfaces provide full control, monitoring and
configuration of the Pump and Transfer Unit via the mapped data points. All of the interfaces
are IP based and share a single 10/100Base-T thernet physical layer which is also shared
with the local HTTP web server. As such, an SNMP, BACnet IP or Modbus TCP client that is
running on an external BMS will need to
‘point to’ the Pump and Transfer Current Local IP
address. This IP address can be found by pressing the
‘up’ key once on the control unit from
the home screen. IP ports for connection are standard for each service (shown above).
Connection to the SNMP V2C agent requires correct community names (shown above).
Connection to BACnet IP requires a correct device number (instance) also shown above. This
device number can be changed by going to the local web server
‘Heat pump ID’ page and
changing the BACnet device number shown.
All data points can be accessed via BACnet
‘Objects’. Analog Inputs, Analog Outputs and
Analog Values and Binary Inputs, Binary Outputs and Binary Values only are implemented.
Object numbers begin at 1 and the maximum number of each data point is shown in notes on
the Web Server
‘Upload’ page. In general the standard BACnet Read property and Write
Property services are available on Analog Output, Analog Value, Binary Output and Binary
Value objects. BACnet Read Property services are available on Analog Input and Binary Input
objects. BACnet Read Object Name is also available on all objects. Mandatory object
properties are implemented but most optional object properties are not. Present value priority
arrays are not implemented for Analog Values or Binary Values. Other optional object
properties and some BACnet services may not be available from the local server.
Unimplemented properties will respond with a BACnet
‘Unknown Property’ error message and
unimplemented services will respond with a BACnet
‘Service Unavailable’ error message.
All data points can also be accessed via Modbus
‘Holding Registers’. Register numbers for
Analog objects can be calculated by multiplying the hundreds, tens and units portion of the
localreg number by two, subtracting one then adding 40,000 and the thousands portion of the
localreg numbers on the xml mapping file (for example, an analog value object localreg
number 2003 would be Modbus holding register 2*3
– 1 + 2000 + 40,000 = 42,005). Register
numbers for Binary objects can be calculated by adding 40,000 to the localreg numbers on
the xml mapping file. Registers are 16 bits long and so 32 bit real (Analog 32 bit floating point)
values are transmitted as two successive 16 bit registers in
‘big endian’ format. Should 32 bit
analog real values received from the Pump and Transfer Modbus TCP interface be
unintelligible on an external BMS then the external BMS may be attempting to send/ receive
32 bit real values with the registers in reverse order. In this case a
‘Modbus Register Swap’
tick box can be set by going to the
‘Network’ page of the Pump and Transfer control unit local
web server and following the
‘Save Network Config’ procedure.
Local Register numbers 2001 to 2999 are Analog Value Objects mostly comprising set-points
that allow the BMS to adjust operating points of the Pump and Transfer unit as necessary. To
be able to change these values SNMP data point 1.3.6.1.4.1.33888.1.6.2.3.0
–
‘P264ControlSetSetparenable’ must be set to 1 if the ‘Network’ page ‘Set-Point Enable
Restrict
’ tick box is checked. If the ‘Network’ page ‘Set-Point Enable Restrict’ tick box is
unchecked, full backward compatibility is maintained with existing Babel Buster interfaces that
may simply write any value to
‘P264ControlSetSetparenable’ to give a 5 minute window for
set-point edits.
The
‘Network’
page
‘Set-Point
Enable
Restrict
’
tick
box
also
affects
1.3.6.1.4.1.33888.1.6.1.1.0
–
‘P264ControlResetRemalmreset’
and
1.3.6.1.4.1.33888.1.6.1.2.0
– ‘P264ControlResetRemsysreset’ in a similar way.
Содержание THW100
Страница 17: ...Heat Pump Manual 17 DIMENSIONS THW30 and THW40 THW50 and THW60 ...
Страница 18: ...Heat Pump Manual 18 DIMENSIONS THW80 THW100 AND THW130 ...
Страница 19: ...Heat Pump Manual 19 DIMENSIONS THWW20 to THWW40 Water to Water THWW50 THWW60 and THWW80 Water to Water ...
Страница 58: ...Heat Pump Manual 58 WIRING DIAGRAM 20kW HEAT RECOVERY COIL ...