Heat Pump Manual
12
TECHNICAL DATA
AIR TO WATER HEAT PUMPS
Model
THW100 and THWDW100
THW100H and
THWDW100H
Nominal heating capacity – kW
100
Duty point in red
20°C Ambient conditions 45°C Water supply 60% RH
Water Supply Temperature
45°C
50°C
55°C
60°C
65°C
70°C
Heating Capacity – kW 10°C Ambient
85.00
83.80
82.80
81.80
81.40
81.08
Power Input
22.00
24.40
27.20
30.00
31.12
32.02
COP
3.86
3.43
3.04
2.73
2.62
2.53
Heating capacity – kW 20°C Ambient
99.20
97.60
96.40
94.60
93.88
93.30
Power Input
22.20
24.60
27.40
30.60
31.88
32.90
COP
4.47
3.97
3.52
3.09
2.94
2.84
Heating Capacity – kW 30°C Ambient
116.40
114.00
111.60
109.80
109.08
108.50
Power Input
22.40
25.00
27.60
30.80
32.08
33.10
COP
5.20
4.56
4.04
3.56
3.40
3.28
Model
THW150 and THWDW150
Nominal heating capacity – kW
150
Water Supply Temperature
45°C
50°C
55°C
60°C
65°C
70°C
Heating Capacity – kW 10°C Ambient
131.2
127.8
123.6
118.8
113.4
107.4
Power Input
33.2
37
41.2
45.8
50.8
56.4
COP
3.69
3.45
3.00
2.59
2.23
1.90
Heating capacity – kW 20°C Ambient
152.2
148.4
144.0
138.8
133.0
126.6
Power Input
35.8
37.2
41.2
46.0
51.6
58.0
COP
4.25
3.99
3.50
3.02
2.58
2.18
Heating Capacity – kW 30°C Ambient
175.6
171.4
166.4
160.6
154.2
147.0
Power Input
36.0
37.2
41.4
46.0
51.0
55.4
COP
4.88
4.61
4.02
3.49
3.02
2.65
Minimum flow requirements across the unit - litres/ second
Model
Across condenser
Across condenser high
water temperature units
>60C
Across evaporator
– water to
water units
7 and 10kW
1.0
2.4
0.8
20kW
1.0
2.4
0.8
30kW
1.5
3.6
1.2
40kW
2.0
4.8
1.6
50kW
2.4
6.0
1.9
60kW
2.9
7.2
2.3
80kW
3.8
9.5
3.0
100kW
4.8
11.8
3.8
130kW
6.2
15.5
5.0
150kW
7.2
18.0
5.8
200kW
9.6
23.5
7.7
Содержание THW100
Страница 17: ...Heat Pump Manual 17 DIMENSIONS THW30 and THW40 THW50 and THW60 ...
Страница 18: ...Heat Pump Manual 18 DIMENSIONS THW80 THW100 AND THW130 ...
Страница 19: ...Heat Pump Manual 19 DIMENSIONS THWW20 to THWW40 Water to Water THWW50 THWW60 and THWW80 Water to Water ...
Страница 58: ...Heat Pump Manual 58 WIRING DIAGRAM 20kW HEAT RECOVERY COIL ...