Texecom Veritas 8 Скачать руководство пользователя страница 15

 

Installation

INS 034-9

15

2.5

 

Commissioning the System (Initial Power Up)

ALWAYS Ensure the mains is off BEFORE removing the front cover

!

 

Connect the black battery lead to the negative (-) terminal of the standby battery and
the red battery lead to the positive (+) terminal of the standby battery. All the indicator
lights will come on. After 10 seconds the zone lights will turn off and a repeating 9
bleep error tone will start.

!

 

Enter the factory set User code

 

%$#"

The error tone will stop.

!

 

Enter the factory set Engineer code 

"#$%

 and press 

,

 to access the

Programming Menu and disable 24 Hour zones (Fire, PA and Tamper) via the
Engineer code. All the zone lights will illuminate.

!

 

Perform a Walk Test as described in section 3.5, page 25. Remember that some
powered detectors (e.g. PIRs and Combined Technology Detectors) take several
minutes to warm up and become operational.

!

 

Test the internal sounder, external sounder and strobe as described in section 3.4,
page 24. To adjust the low-level volume use the control 'pot' on the PCB (see section
2.4.1, page 8), loudness increases anti-clockwise. If the system fails to operate as
expected check that the mounting and wiring are as per the instructions.

!

 

Correct any mistakes and repeat the test (see section 2.7, page 17 on Trouble
Shooting).

!

 

Replace the lid and secure with the two lid screws supplied - 

do not over-tighten.

!

 

Replace the screw covers.

!

 

Press 

-

 to leave the Programming Menu. All the zone lights will turn off.

!

 

The Power light will be flashing to indicate that action is required. Switch on the mains
supply to the control panel. The Power light will stop flashing and stay on
continuously. If the factory settings (section 1.1.1, page 5) are not appropriate then re-
program the system as described in section 3, page 20.

!

 

If you have a meter:

 

Disconnect the battery & check the total non-alarm current is less than 1A.

 

Reconnect the battery & check the total alarm current is not more than 1A.

!

 

The total current is measured as follows:

 

Set your meter to DC current.

 

Connect your meter across F5 (power supply fuse).

 

Remove F5.

 

Record the current drain.

 

Replace F5.

 

Remove your meter.

To avoid accidentally powering down the system be sure to follow 

all

 the

above steps 

in order

.

Installation is now complete and the system is ready for use.

1)

 

If the battery is flat or faulty the RKP may not accept key presses.

2)

 

When the system is full set, after the exit period, the external strobe will flash for
approximately 6 seconds (this option can be de-selected, section 3.2.3, page 22).

Содержание Veritas 8

Страница 1: ...INSTALLATION MANUAL Security Control Panels INS034 9...

Страница 2: ...8 Times 18 2 7 8 Unit Goes Into False Alarm 18 2 7 9 Unit Makes No Sound 18 2 7 10 System Operates but Remote Keypad Makes No Sound 19 2 7 11 The External Sounder or Strobe Does Not Work 19 2 7 12 Th...

Страница 3: ...Basic Log 34 3 15 Programming the Suites 35 3 15 1 Programming the Part Set Suites 35 3 15 2 Programming the Chime Suite 35 3 15 3 Programming the Double Knock Suite 35 3 15 4 Programming the Manual O...

Страница 4: ...s Program Current Time Enter Time HH MM SS Press Program Service Timer 1 Date Enter Date DD MM YY Press Program Service Timer 2 Date Enter Date DD MM YY Press Program Service Timer 3 Date Enter Date D...

Страница 5: ...amper Alarm On 4 Silent Part Set no exit tone on part set Off 5 High Level Chime chime at full volume Off 6 Invert Bell Output negative removed instead of negative applied useful for SCBs Off 7 Final...

Страница 6: ...actory set User code The error tone will stop The Power light will be flashing Enter the factory set Engineer code and press All the zone lights will illuminate Enter The zone lights will turn off The...

Страница 7: ...building mains supply MUST incorporate appropriate short circuit backup protection e g a fuse or circuit breaker of High Breaking Capacity HBC at least 1500A 7 Use mains cable of adequate carrying ca...

Страница 8: ...Installation 8 INS 034 9 2 4 1 Veritas PCB Layouts Figure 1 Veritas PCB Layouts Figure 1a Veritas 8 PCB Figure 1b Veritas 8 Compact PCB Figure 1c Veritas R8 PCB...

Страница 9: ...k 2 Spare PCB fuses are supplied in a press seal bag Fuse Description Rating F1 Battery fuse F1A 250V 20mm F2 Bell Strobe fuse F1A 250V 20mm F3 L S Detector Auxiliary fuse F500mA 250V 20mm F4 RKP Auxi...

Страница 10: ...a built in battery After connecting this battery the sounder will usually sound until its cover is fitted and it is supplied with power from the control panel 5 Terminal B may be programmed as switch...

Страница 11: ...Installation INS 034 9 11 Figure 3d Citadel Defender Figure 3e Volumatic Flashguard Figure 3f Gardiner Technology Novagard 2 Figure 3g Activeguard AU101 Figure 3h CQR Integra HS...

Страница 12: ...the control panel Figure 4 Wiring Magnetic Contacts Figure 4a Wiring a Single Magnetic Contact to a Zone see also Figure 6 Figure 4b Wiring Multiple Magnetic Contacts to a Zone see also Figure 6 Mixi...

Страница 13: ...g Powered Detectors 1 Power is wired in parallel whereas normally closed alarm loops are wired in series normally open alarm loops are wired in parallel 2 Mixing powered detectors and magnetic contact...

Страница 14: ...er connections in addition to the external sounder as follows Terminal Connect To A Siren Positive Supply 12V B Siren Negative Activate Negative Supply 0V 2 4 7 Global System Tamper This is connected...

Страница 15: ...ring are as per the instructions Correct any mistakes and repeat the test see section 2 7 page 17 on Trouble Shooting Replace the lid and secure with the two lid screws supplied do not over tighten Re...

Страница 16: ...dure described in section 3 14 page 34 If it is necessary to remove the lid first switch off the mains supply to the control panel Ensure that the Power light is flashing then use a suitable mains tes...

Страница 17: ...itted in the correct places Check there are no wires shorting to the underside of the PCB Repeated blowing of the battery fuse F1 may indicate a faulty battery 2 7 4 Unit Does Not Accept Code If using...

Страница 18: ...s of 9 bleeps Press The display will illuminate the zones that are about to be armed Press The Tamper light will turn off Press The exit tone and exit timer will start To prevent repeated false alarms...

Страница 19: ...robe make a temporary connection between SAB S and D 2 7 12 The Panic Button Does Not Work Check that the Zone Type of the zone to which the panic button is connected is programmed as PA section 3 9 p...

Страница 20: ...are disabled when the Programming Menu is accessed via an Engineer code 3 To omit zones set chime or change the User code refer to the User Guide 4 The system programming is retained even in the even...

Страница 21: ...cted if older version remote keypads are used 3 2 2 Miscellaneous Selections One From the Programming Menu enter The zone lights of the options currently selected will illuminate Press the appropriate...

Страница 22: ...alarm after 16 invalid key presses when unset Off 5 Random Number Remote Reset RNRR see section 3 2 5 page 23 Off 6 Push To Set see section 3 2 6 page 24 Off 7 Strobe Flash on Full Set On 8 Invert Swi...

Страница 23: ...n an Engineer Reset is required the user can still silence the alarm and cancel the strobe but cannot reset the system 2 RNRR is a method of clearing Engineer Reset It will not function unless at leas...

Страница 24: ...he Programming Menu enter All the zone lights will turn off Enter the desired number of Alarm Activations as a two digit number e g for three Activations enter Zone 1 light will illuminate when the fi...

Страница 25: ...ill sound the quiet exit tone When any zone is opened the corresponding zone light will illuminate The control panel will in addition sound a repeating series of bleeps corresponding to the open zone...

Страница 26: ...g the first 10 seconds after power up 3 7 Programming the Switched Positive Output From the Programming Menu enter The zone light of the function currently selected will illuminate Press the number of...

Страница 27: ...el will configure it as present and illuminate the zone light corresponding to its address To leave configuring press If the configuration has not been updated the panel will sound an error tone The s...

Страница 28: ...hen the panel is set will cause an alarm During entry mode activations of a zone with this Zone Type are disregarded This Zone Type would typically be used for a hall PIR when there is a magnetic cont...

Страница 29: ...switch can be used to full set unset silence an alarm and reset the system 1 Ensure that there are no 24 Hour zones Fire PA and Tamper in fault when using a key switch to reset the system 2 The state...

Страница 30: ...ot omitted by any of the Part Set Suites The system can be programmed to automatically change the Zone Type of any zone into either Exit Entry Inhibited Entry or Guard on part set section 3 10 page 30...

Страница 31: ...be changed into Inhibited Entry Enter The zone lights of the zones which are currently included will illuminate Press the appropriate numbered button s of the zone s to be included or excluded Press T...

Страница 32: ...port of service contracts Disclaimer It is the responsibility of the Installer to obtain prior written agreement from the Customer regarding any use of a Service Timer Texecom accept no liability what...

Страница 33: ...vice Timer Three Lockout From the Programming Menu enter All the zone lights will turn off Enter Service Timer Three Lockout date as a 6 digit number Day Day Month Month Year Year e g to program the 1...

Страница 34: ...off Press The system will chime to confirm that the Seven Event Basic Log has been erased The system will then automatically revert to the Programming Menu and all the zone lights will illuminate 3 14...

Страница 35: ...cally revert to the Programming Menu and all the zone lights will illuminate 3 15 2 Programming the Chime Suite The Chime Suite defines the zones that will be automatically included and excluded omitt...

Страница 36: ...ded from the Manual Omit Suite 2 Zones not included in the Manual Omit Suite will still be omitted if they are excluded in the Part Set Suites 3 15 5 Programming the Zone Disable Suite The Zone Disabl...

Страница 37: ...ve failed Soak Test will be cleared when the Soak Test Suite is programmed If a Soak Test zone activates all subsequent zone activations will be logged as well For example zones 5 6 7 8 are on Soak Te...

Страница 38: ...mm x 55mm Veritas 8 Veritas R8 282mm x 225mm x 80mm 4 3 Environmental Operating Temperature 10 C 14 F to 50 C 122 F Storage Temperature 20 C 4 F to 60 C 140 F Maximum Humidity 95 non condensing see sa...

Страница 39: ...6 Miscellaneous Internal Speaker 50mm 16 Low Level Volume Adjustable High Level Volume 90dB at 1m Loop Response Time Minimum 200ms Maximum 800ms Remote Keypads Up to 6 4 7 Safety Notes 1 Mains voltag...

Страница 40: ...not fit more than one non latching powered detector per zone do not mix unpowered detectors and non latching powered detectors on a zone In order to comply with EN 50131 1 the Entry Time should not be...

Страница 41: ...as corresponds to Inhibit The Zone Disable facility supported by the Veritas corresponds to Isolate 3 When the battery voltage falls below the minimum system operating voltage it will be indicated as...

Страница 42: ...lation Date Zone Zone Type Area Protected Low Loop Resistance Clear High Loop Resistance Fault 1 2 3 4 5 6 7 8 The Instructions MUST NOT be Stored inside the Control Panel 5 2 Maintenance Call Out Rec...

Страница 43: ...er Alarm Systems do you install on average each month Do you have access to the Internet Yes No Are you interested in Upload Download Yes No Are you Accredited NACOSS SSAIB AISC Yes No Do you read Sec...

Страница 44: ...Information Simply complete the form on the reverse of this page and either fax or send it to Texecom to become a Registered Texecom Installer Registration available to UK Professional Installers onl...

Отзывы: