44
cOMMIssIONINg
© TESVOLT We reserve the right to make technical changes. Version RD.TI.015.E.ENG_Installation_Manual_TS48V_v.C.01 Last revised 06/2020
8.2 COMMISSIONING TS 48 V SYSTEMS USING THE MASTER/SLAVE PRINCIPLE
WARNING! Possible damage to the battery due to incorrect configuration.
Incorrect configuration can cause damage to the battery. The parameter settings influence the
SMA Sunny Island’s charging behavior. For this reason, it is important to make the correct settings
during commissioning.
Prerequisites
The SMA Sunny Island has been installed in accordance with SMA’s specifications (installation/connection).
Procedure
1
Check the wiring of the SMA Sunny Island and TS 48 V (see the operating manual for the
SMA Sunny Island).
2
Check the wiring of the components in accordance with section “5.9 Wiring the battery modules” on page
21 et seq. If the wiring is correct, all live components will be protected against physical contact.
3
Ensure the APU is switched off. Insert the tag fuses in the load-disconnecting switch on the Bat fuse
15
/
16
. Fasten the load-disconnecting switch to the bracket in the Bat fuse and close the bracket.
Then close the housing cover on the Bat fuse.
4
Now enter the termination and addressing settings for TS 48 V
TERM
4
and ADDRESS
9
in accordance with the section “Over-
view of all addressing options” on page 51 and the figures in
section “10.2 Expanding capacity using additional TS 48 V units”
on page 48 et seq. In the case of master/slave systems, TERM
4
is to be set to “ON” for APUs of the master and the last stor-
age system in the master/slave configuration. TERM
4
is to be
set to “OFF” for all other slave APUs in the arrangement.
WARNING! Possible damage to the APU due to improper operation.
If you tap on the APU to activate it or confirm an action, you must follow the instructions below to
avoid damaging the APU:
1.
Do not use objects to tap the unit under any circumstances.
2.
Tap gently with your fingers on the marking to the right of the display on the casing.
Never tap on
the display
.
NOTE:
The APU display remains active for approximately two minutes and is then deactivated. It can
be reactivated by tapping twice.
5
Switch on the TS 48 Vs in the reverse order to their position in the
string (slave 3 > slave 2 > slave 1). To do this, first press the ON/
OFF switch SWITCH
15
on the APU LV of the last slave TS 48 V.
The number of battery modules detected is shown on the display.
Tap twice next to the display to confirm the number is correct.
Otherwise, check the BAT-COM cabling.
If present, next switch on the APU LV on slave 2 and then slave 1.
STOP
TERM
ON
OFF
ADRESS
ADDRESS
BATTERY
CHARGER
STOP