11.2.
Parameter settings
The parameters are set by Tennant N.V. The set values are listed below. For the
sake of completeness and if necessary for use by a technician, here follows a
brief description for setting the parameters. However, we advise you not to
alter the parameter settings.
Parameter settings heater
Heater parameters Setting
HC1 H
db1 1
dF1 1
HS1 100
LS1 -30
Table 8: Heater parameters
Parameter settings airco system
Parameters airco system Setting
HC2 C
db2 1
dF2 0
HS2 100
LS2 -30
dn2 3
do2 1
di 3
de2 1
ON2 0
OF2 0
Table 9: Parameters airco system
Setting the parameters
•
Keep set depressed until RE1 (heating) or RE2 (airco system) appears.
Use the arrow keys to switch between RE1 and RE2.
•
•Select RE1 or RE2 and press set once more to change the related parameters.
HC1 (heater) or HC2 (airco system) appears in the display.
•
• Press “Set” again to alter the related setting.
H (heater) or C (airco system) appears in the display.
11.3.
Maintenance of integrated air conditioning/heating system
An air conditioning system is practically maintenance-free.
To prevent problems, the following items need periodical attention:
•
Activate the system at least once a week
.
•
Switch on the system when the engine speed is as low as possible.
•
Weekly check the condenser for dirt and bent lamella that hamper the air flow.
•
Clean the lamella against the air flow.
•
Depending on use, regularly check:
-
the tension and condition of the drive belt
-
the condition of the coolant hoses
•
Regularly check the filter inside the cabin and replace when necessary.
•
Once a year exchange the dryer/filter (rear of cabin).