16.10 Menu Inputs/Outputs
Input/Output D06
Analog inputs
B11 = Condensation:
14.Obarg e 21.5°C
B12 = Evaporation:
14.Obarg e 21.5°C
Having access to this menu it is possible to read several values.
From the screen D01 to the screen D06 it is possible to read the
following probes:
B1: difference between the primary flow and the return liquid
temperature from the plate heat exchanger: it represents
the SUBCOOLING in the heat pump (heating) operation.
B2: temperature of the probe to insert in the puffer of the
system. I the function NoPuffer is activated (from the
Assistance menu) the probe B2 is ignored.
B3: Domestic temperature probe to be entered on the top of
the domestic boiler. If there is one tank working both on
the system and on the domestic, just a probe has to be
used.
B4: return temperature of the system.
B5: flow read by the flowmeter.
B6: compressor head temperature
B7: flow temperature probe of the plate heat/refrigerant gas
exchanger.
B8: Outdoor air temperature.
B9: compressor flow temperature.
B10: compressor suction temperature.
B11: condensation pressure and temperature.
B12: evaporation pressure and temperature.
Mask D07:
management of fan speed and Circulator
speed.
Mask D08:
state of the cooling circuit :percentage of the
electronic expansion valve opening, B10, B12.
Mask D09:
work regime.
•
Capacity demanded.
•
Real capacity.
•
Compressor speed.
•
Waiting time ON: minimum time occurring between 2
turning off, or the time necessary to equalize the pressure
of high and low to the right starting value.
Mask D10:
work zone in the envelope and the countdown
of the alarm “out off envelope”.
Mask D11:
information about pressures.
•
difference between pressure of high and low
•
relation between pressure of high and low
•
alarm “low delta P“ countdown
Mask D14:
temperature of the compressor drain, zone
and state of the envelope.
Mask D15:
overheating of drain compressor and relaitve
type of heating control.
•
SSH = Suction Super Heating
•
DSH = Discharge Super Heating
Mask D19:
Parameters Inverter/Engine
Masck D20:
Parameters Inverter/Engine
Mask D21:
Parameters Inverter/Engine
Masks D30, D31: masks regarding the fan outside battery. You
can find the rpm and the instant power.
Mask D32:
performances.
•
flow
•
delta T (B7 - B4)
•
Electrical power
•
thermal power
•
COP
Mask D33:
summary of unit parameters
16.11 Menu alarm history
Alarm history E02
ALL02 16:02 28/10/13
Power plus off-line
Inlet Outlet
Plant : 18.2°C 17.8°C
Ext. T: 18.0°C
ACS : 20.5°C
Press : Hp 13.0 Lp 13.0
In this menu it is possible to visualize the alarms caused by a
possible intervention of the protection. The alarms list is in the
chapter 13.
16.12 Menu board change
the menu board change allows to visualize other heat pump/s
when they are connected by pLAN and the settings of the
electronico board/panel allow it.
16.13 Menu assistance
The menu Assistance has a submenu structured as follows:
a. Language change
b. Information
c. assistance inputs/outputs
d. Worked hours
e. Config. BMS
f. Param. Assistance
g. Manual management
A. LANGUAGE CHANGE
This menu allow to change the language, where present.
MaskGa01
Possible languages: Italian, English, German and French.
B. INFORMATION
*
This menu contains masks where there are information
concerning the software, control board, valves and nverter,
reserved to the technical assistance.
C. INPUTS /OUTPUTS ASSISTANCE
This menu contains the masks of inputs and outputs reserved to
the technical assistance.
Gc16:
visualize in steps and percentage the opening
of the injection valve.