16.6 Main menu
To enter in the menu press the button
.
Press the buttons and to surf in the menus. At the end of
the operation, press
to come back to the main screen.
The 8 menu as follows:
A.
On-Off unit
B.
Setpoint
C.
Clock/Timetable
D.
Inputs/Outputs
E.
Alarm history
F.
Board change
G.
Assistance
H.
Costructor
16.7 Menu ON-OFF
On/Off Unit A01
Unit Heat-pump
OFF
SUMMER
Mask A01:
set condition and operation mode. When
OFF is set in this menu, it will be always conditioned (es. frost
protection).
Mask A02:
Turn off the pump without conditions for a
certain period of time. Expired the time the function is enabled
again A01.
16.8 Menu SETPOINT
Thermoregulation Unit B01
Temp.HP
Setpoint nominal
(ON)
Cooling:
12.0°C
Heating:
35.0°C
DHW:
60.0°C
Mask B01:
Variation of nominal setpoints.
Mask B02:
Variation of Energy saving setpoints. We
suggest to use Energy saving during the night or during long
absences from home. To reduce the unit consumption it is
suitable to use the climate curve instead of setting the Setpoint,
because it allows a continue erogation.
Mask B03:
activation of antilegionella cycles programs.
Fro the setpoint we suggest 70°C as per manufacturer data.
Mask B05:
choice of fan operation mode.
It is possible to choose between the following states:
•
POWERFULL: it is the most efficient condition, but it
involves also the noise of the major fan.
•
NORMAL: it is the condition of operation set by the
manufacturer, it allows a good compromis between
efficiency and noise.
•
QUIET1 - QUIET2 - SILENT: in these conditions of operation
the fan is slowed respectively of 10, 15, 20 percentage
points. Such conditions allow to work with a more and
more reduced noise. We underline that, setting this
function, the efficiency of the machine is more and more
reduced too
Mask B06:
Just in AIR version. Authomatic mode change
to pass from cooling to heating mode defining a comfort
zone where none of 2 modes are active. To the function be
activated the difference between the setpoints of cooling
and heating has to be the same as the Delta Confort.
Besides it allows to set the operation mode of the inside
fan. The inside fan can follow the demand (compressor
speed) low, medium or high or check the condensation.
Mask B07:
Authomatic Season End. You have to set the
daily average temperature above which the heating function
turns off and the daily average temperature below which the
heating function turns on; if present the domestic function stay
active.
•
En. autoswitch: activate and deactivate the function.
•
HP disable Ext. T.: the daily average temperature above
which the heating function turns off
•
HP enable Ext. T.: the daily average temperature below
which the heating function turns on.
•
Average Ext. T.: the actual daily average temperature.
Mask B08:
optimizer management. The optimizer is
an algorithm permitting to store energy exploiting the thermal
inertia of the building when the conditions are better.
•
Active Optimizer: the function is enabled or disabled.
•
Final Setpoint: Target value of the heat pump with
Delta Optimizer.
•
Delta Optimizer: Delta (positive or negative) due to the
optimization algorithm.
•
Imfluence: minimum value (negative delta) and
maximum (positive delta). This function is used to limit
optimizer influence if necessary.
Mask B09:
set an hysteresis in turning off. Once Setpoint
reached, the machine doesn’t turn off but continues working
at minimum until to reach this target on the setpoint. In the
meantime the demand increase again (ex. demand from the
domestic) the compressor comes back to the operation range
required.