9.3 Installation of the hydraulic part
•
Accurate system washing with clean water filling and
emptying several times. This operation allows to reduce
the number of maintenances and avoid damages to the
exchangers and other components;
•
Prove of the possible losses in the circuit;
•
Isolate all the pipes to reduce heat dispersion and avoid
the formation of condensate;
•
Let the service points free like wells, vent, etc...;
•
Verify water quality is proper, contrary you can have
penalization of the performances, higher flow losses,
possibility of damages.
Reference values: see table section 10.3
9.4 Choice of the system diagram
Make reference to the shown schemes in the following pages to
the realization of the circuit basing on your own exigencies and
adapting it to contest of installation.
WARNINGS!
The buffer, if on outlet pipe, must always comply with a minimum
quantity of liters according to the heat pump KITA used:
KITA S 200 Liters
KITA M 300 Liters
KITA L 500 Liters
WARNINGS!
If you have a pressure drop of more than 7 meters it is mandatory
to use an increased circulator.
WARNINGS!
Probe B2, when used, must always be placed in a buffer mounted
on outlet pipe, never inlet.
WARNINGS!
The following diagrams are purely an example and Templari s.r.l.
will not be responsible for any reason for the plant made at
home. The plant shall be designed and manufactured exclusively
by qualified personnel.