T200H/M and 200EH/EM Menu Trees (05147J DCN7141)
APPENDIX A-7: MODBUS Register Map
A-27
MODBUS
Register Address
(decimal,
0-based)
Description
10
Units
156
12
External analog input 5 slope
eng unit /V
158
12
External analog input 5 offset
eng unit
160
12
External analog input 6 value
Volts
162
12
External analog input 6 slope
eng unit /V
164
12
External analog input 6 offset
eng unit
166
12
External analog input 7 value
Volts
168
12
External analog input 7 slope
eng unit /V
170
12
External analog input 7 offset
eng unit
172
12
External analog input 8 value
Volts
174
12
External analog input 8 slope
eng unit /V
176
12
External analog input 8 offset
eng unit
200
5
O
2
concentration
%
202
5
O
2
concentration during zero/span calibration, just before computing
new slope and offset
%
204
5
O
2
slope
—
206
5
O
2
offset
%
208
5
O
2
sensor cell temperature
°C
300
6
CO
2
concentration
%
302
6
CO
2
concentration during zero/span calibration, just before
computing new slope and offset
%
304
6
CO
2
slope
—
306
6
CO
2
offset
%
308
6
CO
2
sensor cell temperature
°C
MODBUS Floating Point Holding Registers
(32-bit IEEE 754 format; read/write in high-word, low-word order; read/write)
0
Maps to
NOX_SPAN1
variable; target conc. for range #1
Conc. units
2
Maps to
NO_SPAN1
variable; target conc. for range #1
Conc. units
4
Maps to
NOX_SPAN2
variable; target conc. for range #2
Conc. units
6
Maps to
NO_SPAN2
variable; target conc. for range #2
Conc. units
100
3
Maps to
NOX_SPAN3
variable; target conc. for range #3
Conc. units
102
3
Maps to
NO_SPAN3
variable; target conc. for range #3
Conc. units
200
5
Maps to
O2_TARG_SPAN_CONC
variable; target conc. for range
O
2
gas
%
300
6
Maps to
CO2_TARG_SPAN_CONC
variable; target conc. for range
CO
2
gas
%
MODBUS Discrete Input Registers
(single-bit; read-only)
0
Manifold temperature warning
1
Converter temperature warning
2
Auto-zero warning
3
Box temperature warning
4
PMT detector temperature warning
07270D DCN7141
Содержание T200H
Страница 2: ......
Страница 4: ...Teledyne API Model T200H T200M Operation Manual ii This page intentionally left blank 07270D DCN7141 ...
Страница 8: ...Teledyne API Model T200H T200M Operation Manual vi This page intentionally left blank 07270D DCN7141 ...
Страница 10: ...Teledyne API Model T200H T200M Operation Manual viii This page intentionally left blank 07270D DCN7141 ...
Страница 12: ...Teledyne API Model T200H T200M Operation Manual x This page intentionally left blank 07270D DCN7141 ...
Страница 344: ...This page intentionally left blank B 2 07270D DCN7141 ...
Страница 353: ...APPENDIX D 07270D DCN7141 07270D DCN7141 D 1 D 1 ...