Technical equipment of TC600 PLC
93
TXV 138 08.02
No CH1 must be used for the PLC programming, correct the situa-
tion.
Yes Continue at item 6.
5. Do you use channel CH1 for connection?
No Continue at item 10.
Yes
6. Do you use the standard-fitted CH1 RS-232 interface for communica-
tion?
No Continue at item 9.
Yes
7. Do you use CH1 output at connector L?
No CH1 RS-232 interface is led out to connector L, correct the situa-
tion.
Yes
.
8. Do you use the interconnection cable TXK 646 51.06?
No Check connection of your cable.
Yes Continue at item.
9. Do you use CH1 output at terminal board K?
No CH1 optional interface is led out to terminal board K, correct the
situation.
Yes Continue at item 11.
10.
Do you use CH2 output at terminal board N?
No CH2 interface is led out to terminal board N, correct the situation.
Yes
.
11.
Are parameters of the relevant channel set properly?
No Set the parameters (see Article 4.5)
Yes In the case of using CH1 RS-232 or CH2, continue at item 14.
In the case of using the CH1 optional interface
12.
Is the interface converter applied?
No Continue at item 14
Yes
13.
Is the interface converter equipped with indication of the
power supply and state of signals?
No Consider all following possibilities.
Yes, no signal diode is lighted.
Power supply of the converter is not on or the converter is dam-
aged.
Yes, only POWER is lighted.
Error in the PLC or in the cable between the PC and the converter.
Continue at item 14.
Yes, during the data transmission, only TxD blinks, RTS is lighted either
permanently or is not lighted at all.
Fault of the RTS signal between the PC and the converter or the
PC does not support control of the RTS signal necessary for the
RS-485 interface (for RS-232 and RS-422 it is not necessary).
If the software of the PC does not support the RTS signal, it is nec-
essary to set the converter in the mode of automatic switching of
the communication direction, and to set sufficient reply delay at the
central unit (see Article 4.5).
Development environments xPRO, EPOS and some visualization
programs support the RTS signal.
Yes, during the data transmission only TxD and RTS blink.
Fault at the output part of the converter, in the cable between the
controller and the PLC, or possibly in the PLC.
Yes, during the data transmission TxD with RTS and RxD blink al-
ternately.
Communication is correct, the fault is in the cable between the con-
troller and the PC or in the PC.
Continue at item 14.
Checking of the serial
interface converter