![Tecomat TC600 Series Скачать руководство пользователя страница 23](http://html1.mh-extra.com/html/tecomat/tc600-series/tc600-series_manual_1072620023.webp)
Technical equipment of TC600 PLC
23
TXV 138 08.02
5.1.3
Binary Relay Outputs
Binary relay outputs serve for control of two-state action and signalling
elements of the controlled object, supplied by alternating voltage or voltage
higher than the allowed range of closed voltage of transistor outputs. Out-
puts are realized by the closing voltage-free contact relay led out independ-
ently or in a group with one common connector.
Closing of every output is signalled by lighting of the LED diode. The
common LED diode marked as BLK, signals by lighting blocking of outputs
in the still (open) state.
TC601
TC621
TC602
TC622
TC603
TC623
TC604
TC624
TC605
TC625
TC606
TC626
Total number of outputs
-
-
4
10
8
10
Arrangement
(no. of groups x no. of outputs)
1x4
2x4,
2x1
2x4
2x4,
2x1
TC631
TC632
TC633
TC634
-
8
-
-
2x4
Galvanic separation from
other electric circuits
yes
Contact parameters
Closed voltage
max. 250 V
Closed current
max. 1 A
Closed alternating output
max. 250 VA
Closed direct-current output
max. 24 W for voltage 24 V
max. 43 W for voltage 48 V
max. 57 W for voltage 250 V
Current through the group
common conductor
max. 4 A
Closing and opening time
typ. 5 ms
Oscillation time
typ. 1 ms
Mechanical life
min. 20 x 10
6
closings
Servicing of inductive load
external
Protection of the contact
against overload
external
Dielectric resistance of the
open contact
1 kV~
Dielectric resistance between
relay contacts and non-live
PLC parts
2.2 kV~
Dielectric resistance between
relay contacts and SELV cir-
cuits
3.75 kV~
Dielectric resistance between
contact groups
1)
3.75 kV~
1)
Including contacts led out independently
Parameters of relay
outputs