Technical equipment of TC600 PLC
13
TXV 138 08.02
4.4 Serial Communication Channels
Standard design of all PLC's of the TC600 series is equipped with two
communication channels. Third communication channel is added per order
(see Article 2.5).
4.4.1
Serial Communication Channel 1 (CH1)
CH1 is designed for connection of the PLC to a superior system. The su-
perior system most often represents a computer of the PC class performing
the function of a programming device, visualisation station or control device
of the PLC network. It contains a complete set of the EPSNET network
services. Detailed description of the services is given in the handbook
Serial
Communication of Tecomat Programmable Logic Controllers,
TXV 001 06.02.
CH1 is equipped with fixed fitted interface RS-232 without galvanic sepa-
ration from internal circuits. Besides this, in all types of BM, CH1 can be
complemented with a piggyback with interface RS-485 or RS-422. Optional
interface is implicitly assigned to CH1. Interface RS-232 is assigned to CH1
automatically by connecting the cable TXK 646 51.06. Together with con-
necting interface RS-232, the optional interface (if fitted) is disconnected
from CH1. For selection of the interface type, especially function of the su-
perior device is decisive, type of interface of its serial communication chan-
nel, connection distance, transmission speed and level of disturbances.
4.4.1.1 Interface RS-232
Interface RS-232 ensures conversion of output signals of TTL level to
level defined by the specification V.28 (EIA RS-232), and of input signals
according to V.28 to the TTL level. It allows for connection of two end de-
vices in the duplex mode. It is suitable for connection realised in short dis-
tance in an environment with low level of electromagnetic disturbances.
For the communication, PLC's of the TC600 series use only binding cir-
cuits of signals TxD (Transmit Data), RxD (Receive Data), CTS (Clear To
Send), and RTS (Request To Send) of the standard RS-232 interface.
Transmission speed
max. 230.4 kBd
1)
Cable length
max. 15 m
2)
Voltage of outputs TxD, RTS for level 1
typ. -8 V against GND (R
l
=5 k
Voltage of outputs TxD, RTS for level 0 typ. +8 V against GND (R
l
=5 k
Voltage of inputs RxD, CTS for level 1
min. -3 V against GND
max. -25 V against GND
Voltage of inputs RxD, CTS for level 0
min. +3 V against GND
max. +25 V against GND
Impedance of inputs RxD, CTS
5 k
1)
The maximum transmission speed is limited by the maximum allowed
transmission speed of the set mode of the communication channel.
2)
The maximum cable length may only be used provided that the maxi-
mum transmission speed is reduced.
To program the PLC,
communication
channel CH1 is used
Interface RS-232 of
CH1 is activated after
connection of the
interconnecting cable
TXK 646 51.06
Interface RS-232 is
used for two-point
connection
Parameters of the
RS-232 interface