Tecomat TC600
TXV 138 08.02
26
Scanner type
(can be selected by a program)
Pt100
W
100
= 1.385
Pt100
W
100
= 1.391
Ni1000 W
100
= 1.617
Ni1000 W
100
= 1.500
general 0 to 630
general 0 to 2520
Measurement range
see table 5.1a
Resolution
see table 5.2a
Format of input data
see table 5.1a
Total measurement error
see table 5.3a
Temperature drift
see table 5.3a
Input resistance
>10 M
Resistance of the signal source
max. 8 k
Input voltage
1)
max.
12 V
Current of the power supply for sup-
plying of scanners
1 mA
Load resistance of the current supply
2)
max. 8 k
1)
Greatest voltage difference measured among all input clips of the mod-
ule may not exceed this value.
2)
The given load may be connected to both output clips of the current sup-
ply (IoutA, IoutB).
Measurement range
(can be selected by a program)
0 mA to +20 mA
+4 mA to +20 mA
Resolution
see table 5.2b
Format of input data
see table 5.1b
Total measurement error
see table 5.3b
Temperature drift
see table 5.3b
Input resistance
25.2
Input current
max. 50 mA
Input voltage
max. 5 V
Measurement range
(can be selected by a program)
0 V to +10 V
0 V to +2 V
Resolution
see table 5.2b
Format of input data
see table 5.1b
Total measurement range
see table 5.3b
Temperature drift
see table 5.3b
Input resistance
>10 M
Resistance of the signal source
max. 10 k
Input voltage
1)
max.
12 V
1)
Greatest difference of voltage measured among all input clips of the mo-
dule may not exceed this value.
Value of the input variable is passed in one of three formats. Format of
input data is selected in a program.
In the FS format (Full Scale), value 0 of input data corresponds with the
lower limit of the measurement range, the maximum value of input data
65535 corresponds with the upper limit of the measurement range. Ex-
ceeding of the range of the converter is not signalled. Conversion to tech-
nical units is performed on the user program level. The FS format provides
the highest possible resolution.
In the Technical units format, converted value of the input variable is
passed in
C,
,
A or mV. Exceeding of the range is signalled by value
Parameters of inputs
for TC634 resistance
temperature scanners
Parameters of TC634
current inputs
Parameters of TC634
voltage inputs
Formats of input data
Format FS
Technical units