Technical equipment of TC600 PLC
19
TXV 138 08.02
Tab. 4.2 List of available transmission speeds of CH1, CH2 and CH3 in
various modes
Speed
Channel mode
Speed
Channel mode
0.3 kb/s
PC,MAS
28.8 kb/s
PC,PLC,MAS
0.6 kb/s
PC,MAS
38.4 kb/s
PC,PLC,MAS
1.2 kb/s
PC,MAS
57.6 kb/s
PC,PLC,MAS
2.4 kb/s
PC,MAS
76.8 kb/s
PLC
4.8 kb/s
PC,MAS
115.2 kb/s
PLC
9.6 kb/s
PC,PLC,MAS
172.8 kb/s
PLC
14.4 kb/s
PC,PLC,MAS
230.4 kb/s
PLC
19.2 kb/s
PC,PLC,MAS
When setting the parameter reply delay (in the PC mode) or transport
delay (in the MAS mode), a message of the following type is shown on the
display
with the following meaning:
t
- setting of the reply delay
2 - number of the channel being set
10 - set delay/transport delay in ms
By shortly pressing the SET button, we increase the value of the de-
lay/transport delay by 1, by pressing and holding the SET button (for about
1s) we increase its value by 10. By pressing the MODE button we save the
set value and move to setting of another parameter.
Optional reply delay serves for solution of situations when the superior
system sending the message, cannot switch in time from transmission mode
to receiving mode, and thus it cannot receive the PLC's reply. By extending
the reply delay the superior system gains time for preparation necessary to
start receiving of a reply.
The delay time is set in ms and may take values from 0 to 99 ms. Value
0 means that the minimum reply delay shall correspond with the time neces-
sary to transmit 1 byte, thus it depends on the set speed. Values 1 to 99
give the delay in milliseconds and are not dependent on the communication
speed.
The reply delay is set only for mode PC.
Optional transport delay serves for solution of situations when the PLC in
the role of the superior system is waiting for reply from a subordinate PLC
for longer than 0.5 s for the reason of delay on the transmission line, caused
by modems etc.
Transport delay is set in multiples of 100 ms and may take values from 0
to 6 s. Value 0 means that the superior PLC waits for the reply for the
maximum of 0.5 s (time of cycle of the subordinate PLC may not exceed
this value). Values 1 to 60 give the transport delay of 0.1 to 6 s which is
added to the value 0.5 s. Values 61 to 99 set the maximum transport delay
of 6 s.
The transport delay is set only for mode MAS.
When setting the parameter CTS signal detection, a message of the
following type is shown on the display
with the following meaning:
CTS
- setting of the CTS signal detection
2
- number of the channel being set
on
- detection on
Setting of the reply
delay and transport
delay
Reply delay
Transport delay
Setting of the CTS
signal detection