![Tecomat TC600 Series Скачать руководство пользователя страница 9](http://html1.mh-extra.com/html/tecomat/tc600-series/tc600-series_manual_1072620009.webp)
Technical equipment of TC600 PLC
9
TXV 138 08.02
3.2 Operational Conditions
Class of environment effect
33 2000-3
(mod IEC 364-3:1993)
Range of operational tempera-
tures
0 °C to +55 °C
Average temperature during 24
hours
max. +50 °C
Allowed transportation tem-
perature
-25 °C to +70 °C
Relative air humidity
50 % to 95 % without condensation
Degree of pollution
(idt EN 61131-2:1992, IEC 1131-2:1992)
Overvoltage category of in-
stallation
33 0420
(eqv IEC 664:1980, IEC 664A:1981)
Immunity against disturbances
(idt EN 61131-2:1992, IEC 1131-2:1992)
(tab. 16)
Emitted disturbance
levels for group 1, class A
(mod CISPR 11:1997)
Vibrations
Fc 10 Hz to 150 Hz, 0.15 mm, 10 cycles
!
(idt EN 60068-2-6:1995,
IEC 68-2-6:1995+Corr.1995)
Operating position
vertical
Type of operation
permanent
3.3 Basic Parameters
BM
EM
EM/2
Type of appliance
to be built-in
Class of el. object
(mod IEC 536-1:1976, IEC 536-2:1992)
Coverage
IP-10B
Supply voltage
(SELV)
24 V~ ±20 %,
50-60 Hz ±5 %
or 24 V- ±20 %
Power input
max. 20 VA
or 13 W
1)
Mass
about 0.8 kg
about 0.4 kg about 0.2 kg
Size (h x w x d)
2)
141x182x69
141x157x44
141x89x44
1)
Power input of BM extended by one EM and one EM/2
2)
See figs. 9.1, 9.2, 9.3