Tecomat TC600
TXV 138 08.02
92
08 00 00 00
exceeding of the first limit of guarding the cycle time
The cycle time has been longer than the set warning value.
09 00 00 00
wrong system time of the RTC circuit
The current time must be written from the superior system.
11.4.3 User Program Errors
These errors can be treated as needed in the user program either by
eliminating the cause by checking input parameters before executing of the
given instruction or by treating the consequence.
10 00 00 00
division by zero
Divisor in the division instruction equal to 0.
11 00 00 00
initial index for WMS instruction lies outside of table T
WMS instruction has a wrong parameter and therefore it will
not be executed.
12 00 00 00
initial index for LMS instruction lies outside of table T
LMS instruction has a wrong parameter and therefore it will
not be executed.
13 00 00 00
table instruction above the scratchpad has exceeded its
range
Table defined by the table instruction above the scratchpad
has exceeded its range. Instruction will not be executed.
14 00 00 00
source block of data defined outside of the range
Source block of data for the move instruction has been de-
fined outside the range of the scratchpad, data or table. In-
struction will not be executed.
15 00 00 00
target block of data defined outside of the range
Target block of data for the move instruction has been de-
fined outside the range of the scratchpad or table. Instruc-
tion will not be executed.
11.4.4 Errors in the Peripheral System
22 00 00 00
overflow of the internal stack from interrupt inputs
40 00 50 00
overloaded outputs
11.5 Solution of Communication Problems with the Supe-
rior System
Connection of the PLC to a superior system, usually a PC, is a necessity
as every PLC must be programmed. Possible problems and way of their
analysis is indicated on the following lines.
1. Is the power supply led to the PLC?
No Correct the situation.
Yes
2. Has the PLC passed the starting sequence and is in the RUN mode
or HALT?
(see Article 10.3)
No An error has occurred in testing of the system kernel, communica-
tion is not possible, it is necessary to repair the PLC.
Yes
3. Do you want to program the PLC using the xPRO development environ-
ment?
No Continue at item 5.
Yes
4. Do you use channel CH1 for programming?
Programming errors
Checking of the PLC