![Tecomat TC600 Series Скачать руководство пользователя страница 33](http://html1.mh-extra.com/html/tecomat/tc600-series/tc600-series_manual_1072620033.webp)
Technical equipment of TC600 PLC
33
TXV 138 08.02
inductive loads should be serviced in the place of origination of the dis-
turbance
Principle of various ways of servicing the inductive load, aids for the de-
sign of RC disturbances elimination elements, overview of sets of distur-
bances elimination elements supplied by the PLC producer and other rec-
ommendations are given in the handbook
Design of Tecomat
Programmable Logic Controllers, TXV 001 08.01.
9.2 Ensuring of the Required Operational Temperature
In cases without forced inside air circulation, the PLC must be placed in
such a way so that the distance between the bottom and top side of the PLC
and inside sides of the case is at least 100 mm. If this cannot be ensured by
good unprompted air circulation, it is necessary to ensure air circulation by
building in a ventilator. The maximum allowed air temperature entering the
regulator is 55 °C. The PLC itself participates in the output losses by the
maximum of 13 W (20 VA) of the power input, typically the loss of 0.25 W at
every closed binary input and 0.2 W at every closed transistor output.
Losses at closed relay outputs are included the PLC power input.