![Tecomat TC600 Series Скачать руководство пользователя страница 17](http://html1.mh-extra.com/html/tecomat/tc600-series/tc600-series_manual_1072620017.webp)
Technical equipment of TC600 PLC
17
TXV 138 08.02
4.5 Setting of CPU Parameters
CPU parameters are set in the setting mode (mode SET). To set and
display parameters, the PLC front board is equipped with buttons SET and
MODE and a one-place seven-segment LED display.
In the SET mode, all data are displayed in the rotational way, that is,
number 123 is displayed in such a way that digits 1, 2, 3 are lighted gradu-
ally on the display, then there is a delay, and the whole sequence is re-
peated. Every character is displayed for about 0.5 s and is separated from
the following character by a delay which ensures recognition of two identical
characters displayed one after another (for example, displaying of the num-
ber 111).
Switching to the SET mode can be performed by pressing buttons SET
and MODE simultaneously while the PLC power supply is on. Buttons SET
and MODE are held pressed until the triple dash
appears on the display. In
general it holds that by the SET button we change setting of the parameter,
and by the MODE button we move through individual parameters. Pressing
of the button is indicated by lighting of the decimal point on the display.
The SET mode may be terminated any time by simultaneously pressing
the buttons SET and MODE. We again hold the buttons SET and MODE
pressed until the triple dash
appears on the display. State of parameters is
saved upon termination of the mode in the power-independent memory of
parameters, and the PLC switches to the HALT mode or some of error mes-
sages may possibly be signalled.
Tab. 4.1 Adjustable CPU parameters
(ordered from the left to the right and in the rows)
Object to
be set
Adjustable parameters
channel CH1
-
address
speed
delay of re-
ply
CTS detec-
tion
off
-
-
-
-
mode PC address
speed
delay of re-
ply
CTS detec-
tion
channels
reg. PLC address
speed
-
-
CH2 and CH3
1)
mode
MAS
-
speed
transport
delay
CTS detec-
tion
2)
reg. uni
-
-
-
-
Program source
memory
off
on
1)
Only BM's fitted with the communication piggyback contain channel
CH3.
2)
CTS detection in the MAS mode cannot be set for CH3.
4.5.1
Setting of Parameters of Serial Communication Channels CH1,
CH2, CH3
Channel CH1 has fixed-set mode PC which cannot be changed. In this
channel, the parameter serial channel mode is not set.
In setting the parameter serial channel mode for channels CH2, CH3, a
message of the following type is shown on the display
with the following meaning:
C - setting of the serial channel mode
2 - number of the channel being set
off - the mode being set
Serial channels may operate in the following modes:
Mode SET
Displaying of
parameters
Entrance in the SET
mode
Termination of the
SET mode
Adjustable
parameters
Setting of the serial
channel mode