Fn_97:
Fault Control Set-up
xxx0:
Fault contact is not energized during auto restart operation
xxx1:
Fault contact is energized during auto restart operation
xx0x:
Fault contact is not energized during momentary power loss detection
xx1x:
Fault contact is energized during momentary power loss detection
x0xx:
Fault contact is not energized after external emergency stop signal is received
x1xx:
Fault contact is energized after external emergency stop signal is received
0xxx:
Fault contact is not energized during external base-block
1xxx:
Fault contact is energized during external base-block
Fn_98:
Fault Contact Set-up
xxx0: Fault contact is not energized after over-torque (OL3) is detected
xxx1:
Fault contact is energized after over-torque (OL3) is detected
xx0x:
Fault contact is not energized after electronic over-load (OL1) is activated
xx1x:
Fault contact is energized after electronic over-load (OL1) is activated
x0xx:
Fault contact is normal open (N/O)
x1xx:
Fault contact is normal close (N/C)
0xxx:
Fault contact is not energized after electronic over-load (OL2) is activated
1xxx:
Fault contact is energized after electronic over-load (OL2) is activated
Note:
When (Fn_97) is set to (xxx0), During the auto restart operation the fault contact will not be
energized until (Fn_35 (auto restart times) decreases to 0. (OL1 / OL2 / OL3)
Fn_100: Communications I.D. Number:
1
~
32
Fn_101: Baud rate of Communication: (bps)
0: = 4800
1: = 9600
2: = 19200
3: = 38400