41
Fn_34: Auto Restart Interval: 0.1 ~ 800 sec
Fn_35: Number of Auto Restart Attempts (0 -10) times
1. When Fn_35=0, the inverter will not auto-restart after a malfunction break away from
operation. (Except for momentary power loss, please refer to Fn_31/32 for details)
2. When Fn_35>0, Fn34=0: The inverter will use speed search to pull the frequency back to the
frequency before the trip from free status in 0.5 second and then accelerate or decelerate to
preset frequency. (Except for momentary power loss, please refer to Fn_31/32 for details).
3. When Fn_35>0, Fn34>0: The inverter will free run for a certain period (ser by Fn_34) and
then accelerate or decelerate from Fn_42 to preset frequency. (Except for momentary power
loss, please refer to Fn_31/32 for details)
4. The number of Auto Restarts will be reset under the following conditions:
(1). Fault is not detected for 10 minutes (either in Run or Stop Mode).
(2). Press “RESET” Key or reset terminal of
TM2
.
Display Meter Control
(Meters)
Fn_36: Numbers of motor poles = 2 - 72 poles
(Meters)
Fn_47 = xxx0 :
Output Voltage display
disable
xxx1 :
Output Voltage Display
enable
xx0x :
DC Voltage Display
disable
xx1x : DC Voltage Display
enable
x0xx
:
Output
Current
disable
x1xx : Output Current
enable
(Meters)
Fn_51:
Displays frequency in (Hz); (Pre-set frequency) (Operation frequency)
0. Displays Frequency in (Hz)
1. Displays RPM of motor; numbers of poles set by Fn_36.
2. Line speed display mode: in integral (xxxx)
3. Line speed display mode: in one digit decimal (xxx.x)
4. Line speed display mode: in two digits decimal (xx.xx)
5. Line speed display mode: in three digits decimal (x.xxx)
(Meters)