Fn_10: Start / Stop Control
This parameter is used to decide if the Start and Stop function will be controlled by the Keypad or
remote control TM2 (terminal 3 / 4).
0 : Keypad control
1 : Remote control TM2 (terminal 3 / 4 )
Note:
z
When Fn_10=1, please refer to the descriptions of Fn_31/32/34/35, in order to avoid the
damage to the human and the machine.
z
The STOP key on the Keypad can still be used for emergency stopping even if the start / stop
control is from terminal 2 (Fn_10 =1). (Refer to Fn_48)
Fn_11: Frequency Command Selection
0 : Run by Fn _25 Master Reference
1 : Run by Speed Pot on Keypad
2 : Run by Speed Pot on TM2 (terminal 12 / 13 / 14)
3 : Run by multi-function input freq. command (terminal 6 / 7 / 8)
0 – 10 Vdc Speed Ref. 0 – 5 Vdc External 4 – 20mA Signal 0 – 10 Vdc External
(Fn_11) to 2
Use a (10K) (2 Watt)
Pot with the wiper in
Term (13)
Jumper (JP1)
pins 1&2
(Fn_11) to 2
For a Remote 5 Vdc
Signal
Jumper (JP1)
Pins 1&2
(Fn_11) to 2
For a Remote Signal
4 ~ 20mA
Jumper (JP1)
Pins 2&3
(Fn_11) to 2
For an External Signal
0 – 10 Vdc
Jumper (JP2)
Pins 2&3