![TECO T-verter N2 Series Скачать руководство пользователя страница 13](http://html1.mh-extra.com/html/teco/t-verter-n2-series/t-verter-n2-series_operation-manual_1072474013.webp)
10
Functional Specification:
Carrier frequency
1 - 12 K
Frequency Control Range
0.1 – 400 Hz
Frequency Accuracy
Digital: 0.01% (-10 ~ 40
°
C); Analog: 0.4% (25+-10
°
C)
Frequency Resolution
0.01 Hz with computer or PLC control, 0.1 Hz with keypad control when freq.
above 100 Hz
Frequency Setting Signal
(0-5VDC) (0-10VDC) (4-20mA) (0-20mA)
Accel / Decel Time
0.1-3600 SEC with (2) S-curves
Braking Torque
About 20% (built-in Braking transistor)
C
ont
rol
Characteristics
V/F Pattern
18 patterns, one curve programmable
Instantaneous Over Current
Approx. 200% rated current
Overload
T-verter: 150% / 1 minute
Motor Overload Protection
Electronic thermal overload relay
Over voltage
200V series: (DC bus voltage exceeds 427V)
400v series: (DC bus voltage exceeds 854V)
Under voltage
200V series: (DC bus voltage drops < 200V)
400v series: (DC bus voltage drops < 400V)
Momentary Power Loss
0~2 seconds: The T-verter can be restarted using the speed search feature
Heat Sink Fin Overheat
Protected by thermister
Prot
ect
ion
Funct
ion
Ground Fault
Electronic circuit protection
Operation signals
Forward/Reverse operation, by keypad or hardwire contact, multiple individual
commands
Reset
Released protection while the protective function is operating
Input
Signal
Multifunction Input
Refer to function illustration in Fn_56
Multifunction Output Refer to function illustration in Fn_61
Output
Signal
Fault output
250VAC 1A, 30VDC 1A or less
Built-in Function
Frequency reference bias/gain; up/lower limit; manual torque boost; frequency
meter calibrating gain; auto restart attempt; skip frequency; S-curve
ACCEL/DECEL; Carrier frequency adjust.(1-12KHz)
Communication link function
Digital operator monitor
Frequency command, output frequency, speed, output current, output voltage,
P-N bus voltage, rotating direction
Operation
C
ondi
ti
ons
Analog Output Monitor
Analog output (0-10V), possible to select output frequency & setting freq. &
output voltage & P-N bus voltage
Location
Indoor (protected from corrosive gas and dust)
Ambient Temperature
-10 degrees ~ 40 degrees © 50 degrees with cover removed
Humidity 0-95%(non
condensing)
Envi
ron
mental
Vibration 0.5G
Enclosure
IP20 / IP65 (NEMA4)
EMC
EN50081-1, EN50082-2 (with optional filter)
LVD EN50178
UL UL
508C
z
N2-205 and above capacity are not CE complied