46
00 : SP1 (Multi-speed 1)
:
Please refer to (Fn_17)
01 : SP2 (Multi-speed 2)
:
Please refer to (Fn_17)
02 : SP3 (Multi-speed 3)
:
Please refer to (Fn_17)
03 : Jog operation
Please refer to (Fn_17)
04 : Accel. / Decel. Time selection
Please refer to (Fn_01)
05 : External Emergency Stop
06 : External Base Block Command
07 : Speed search :
Please refer to (Fn_48)
08 : Energy saving mode :
Please refer to (Fn _82)
09 : Control Signal Selection
10 : Communication Control Mode Selection
11 : Accel. / Decel. Prohibit
12 : UP command
13 : DOWN command
14 : Sequence control
:
Please refer to (Fn_17) (Fn_84) ~
(Fn_91)
15 : Master / Auxiliary speed selection :
Please refer to (Fn_11)
16 : (N/O - normal open contact) to (N/C - normal close contact)
Note:
(Fn_56) will be ineffective when Terminal 6 is used for 3-wire control There are 32 combinations
that can be selected as above by terminals 6, 7, 8, (Fn_56) (Fn_57) (Fn_58)
05 External Emergency Stop
As soon as external emergency stop signal is received, the T-verter will Decel. to a stop
(regardless of the setting in (Fn_44) the display will blink "E.S." After this signal is removed,
either turns OFF and ON the RUN command again to reset. The in verter will restart from the start
freq. If the Emergency stop signal is removed before the T-verter stops, T-verter will still execute
the emergency stop.
06 External Base Block Command
The Base Block Command can be found in the Multifunction input assignment group (6), As soon
as Base Block signal is applied, the T-verter output is shut off regardless of the setting in (Fn_44)
and the display will blink "b.b.". After the base block input is removed, either turn OFF and ON
again run command, or to press the RUN key and the T-verter will restart from the start freq.
The Fault contact is controlled by Fn_97:
When Fn_97=0xxx Fault contact is not energized after external base block
When Fn_97=1xxx Fault contact is energized after external base block