![TECO T-verter N2 Series Скачать руководство пользователя страница 25](http://html1.mh-extra.com/html/teco/t-verter-n2-series/t-verter-n2-series_operation-manual_1072474025.webp)
22
Parameter List
Function
Fn_
xx
Description Set
Unit
Range
Factory
Setting
Page
Drive Capacity
0 Drive Capacity Selection
1
1-40
*3
30
Accel. Time
1 Accel. Time 1
0.1 sec
0.1-3600 sec 10 sec*1
30
Decel. Time
2 Decel. Time 1
0.1 sec
0.1-3600 sec 10 sec*1
30
Stop / Start
Control
Terminal 2
3
xx00 : FWD/STOP, REV/STOP
xx01 : FWD/REV, RUN/STOP
xx10 : 3 wire Start / Stop Control
x0xx : REV Command Enable
x1xx : REV Command Disable
0xxx : Setting frequency will remain at last output frequency when
T-verter stops and Fn_11 = 3
1xxx : Setting frequency will be 0 (zero) when T-verter stops and
Fn_11 = 3
0000 31
Parameter
Lock Out
4 xxx0 : Enable
(Fn_17 - 25)
xxx1 : Disable
(Fn_17 - 25)
xx0x : Enable (Functions except
Fn_17 - 25)
xx1x : Disable (Functions except
Fn_17 - 25)
0000 32
V/F Pattern
5 V/F pattern selected
1
0-18
9 / 0*4
32
Freq. Limit
6 Freq. output upper limit
0.01 Hz
0-400 Hz
60 / 50*4 34
Freq. Limit
7 Freq. output lower limit
0.01 Hz
0-400 Hz
0 Hz
34
8 Up-to desired frequency setting
0.01 Hz
0-400 Hz
0 Hz
34
Target Speed
Detection
9 Up-to frequency setting detection width (+/- Fn_9) 0.01 Hz
0-30 Hz
0 Hz
34
Start / Stop
Selection
10 0 : Controlled by Keypad
1 : Controlled by
TM2
0 35
Freq. Command
Selection
11 0 : Controlled by (Fn_25) Master Reference at Keypad
1 : Controlled by VR on Keypad
2 : Controlled by VR on
TM2
(terminal 12-14) or analog signal.
3 : Controlled by TM2 using multi-function inputs 6-7-8(see Fn_56~Fn58)
0 35