TMSL 097-44018-26
Issue 2: Sep 99
Page 98
COMMAND CODE: RTRV-EQPT (Contd)
RESPONSE FORMAT (Contd)
EXAMPLE
Input:
RTRV-EQPT::TO-5:134;
Response:
SANJOSE-114 1997-12-08 15:04:13
M
134 COMPLD
“TO-5:FAS,INH,MN,,,,"
This example, tagged as command 134, displays port 5 of timing output card 5 as: framing = FAS, all
outputs will be squelched upon card failure, and a minor alarm will be generated upon port failure.
aid
parameter
value
meaning
TO-c
framing
CAS
channel associated signaling
CAS4
channel associated signaling with cyclic redundancy check 4
CRC4
common channel signaling with cyclic redundancy check 4
D4
D4 framing
ESF
ESF framing
FAS
common channel signaling
troublecode
ALW
AIS is sent on all outputs upon card failure
INH
all outputs are squelched upon card failure
Note: If any port on the TO card is set for ANALOG, the troublecode must be set
to INH.
portseverity
MJ
port failure causes major alarm
MN
port failure causes minor alarm
osc1
(null)
(not applicable)
osc2
integration
clklevel
alarmlead
signaltype