![Swan Analytical Instruments AMI Codes-II O3 Скачать руководство пользователя страница 79](http://html1.mh-extra.com/html/swan-analytical-instruments/ami-codes-ii-o3/ami-codes-ii-o3_operators-manual_1411369079.webp)
A-96.250.881 / 070622
AMI Codes-II O3
Program List and Explanations
79
5.3.2.22
Parameter:
Choose on of the following process values.
DIS
Sample Flow
5.3.2.32
Settings
:
Choose the respective actuator:
Time proportional
Frequency
Motor valve
Examples of metering devices that are driven time proportional are
solenoid valves, peristaltic pumps.
Dosing is controlled by the operating time.
5.3.2.32.20
Cycle time:
duration of one control cycle (on/off change).
Range: 0–600 sec.
5.3.2.32.30
Response time:
Minimal time the metering device needs to react.
Range: 0–240 sec.
5.3.2.32.4
Control Parameters
Range for each Parameter same as
Examples of metering devices that are pulse frequency driven are
the classic membrane pumps with a potential free triggering input.
Dosing is controlled by the repetition speed of dosing shots.
5.3.2.32.21
Pulse frequency:
Max. pulses per minute the device is able to re
-
spond to. Range: 20–300/min.
5.3.2.32.31
Control Parameters
Range for each Parameter same as
Dosing is controlled by the position of a motor driven mixing valve.
5.3.2.32.22
Run time:
Time needed to open a completely closed valve
Range: 5–300 sec.
5.3.2.32.32
Neutral zone:
Minimal response time in % of the runtime. If the re
-
quested dosing output is smaller than the response time, no change
will take place.
Range: 1–20 %
5.3.2.32.4
Control Parameters
Range for each Parameter same as
5.3.2.32.1
Actuator = Time proportional
5.3.2.32.1
Actuator = Frequency
5.3.2.32.1
Actuator = Motor valve