XLINK 500/100 Operations & Maintenance Manual page # 102
To log the daily temperature
and
the hourly temperature, only one physical temperature sensor
is needed. Set up two measurements with the same setup; change the
Measurement Interval
and
the A
veraging Time
and use a different
Label
for each. One would happen once a day
(
Measurement Interval
24 hours, A
veraging Time
24 hours), and the other once an hour
(
Measurement Interval
1 hour, A
veraging Time
1 hour). It would be a good idea to set up the
sampling Interval to one minute for both sensors in order to save power (See page 74).
If two separate measurements are scheduled to measure the same sensor at the same time (as
they will in the examples above), only one reading of the sensor is made, and the result is shared
by both measurements.