XLINK 500/100 Operations & Maintenance Manual page # 32
4.16.
Connecting Thermocouples
Thermocouples connect to the C or D channels as shown below.
The key settings for thermocouples are:
Measurement Type: Analog
Analog type: Diff C, D or E.
Input Range: 39mV with Bias
Equation: 24716*X+Terminal_temp {K type thermocouple, -8C to 64C}
For more accurate results, here are some other K-Type Equations:
Linear delta T range of ± 20°C. Approximation error is ±0.20°C.
Temp (°C) = 25.346 * X*1000
–
0.1114 + Terminal_temp
Linear delta T range of ± 40°C. Approximation error is ±0.83°C.
Temp (°C) = 25.419 * X*1000
–
0.3847 + Terminal_temp
3
rd
order Poly delta T range of ± 20°C. Approximation error is ±0.01°C
Temp (°C) = Poly((X*1000), (Terminal_temp -0.0107), 25.263, -0.4443, 0.2053)
3
rd
order Poly delta T range of ± 40°C. Approximation error is ±0.03°C
Temp (°C) = Poly((X*1000), (Terminal_temp -0.0115), 25.326, -0.4305, 0.0861)
T-Type Equations:
Linear delta T range of ± 20°C. Approximation error is ±0.30°C.
Temp (°C) = 25.892 * X*1000
–
0.151 + Terminal_temp