6 Electrical Connection
User Manual
40
Fig. 6-5
Communication configuration
Inverter operation information can be transferred to the PC of the installed
monitoring software (e.g. SolarInfo Insight) or to a local data logging device (e.g.
SolarInfo Logger) through RS485 communication connection.
Prepare communication cable and RJ45 plug before communication connection.
RS485 communication cables should be:
Shielded twisted pair cables or Shielded twisted pair Ethernet cable.
A converter such as RS485-232 converter or SolarInfo Logger is needed
to convert signal between inverter and PC.
Network interface is an optional function. Contact Sungrow if necessary.
6.5.2 RS485 Communication System
For Single Inverter
Where there is only one inverter, a RS485 cable can guarantee the communication
connection.