10 Operation of LCD Display
User Manual
76
10.10.4 Reactive Power Setting for Italy
If the “Countries” selected is “IT” (Italy), several LCD menus and operation methods
are different from other countries.
The differences focus on “Run-param” as shown below.
Italy “Q(P)” Mode
Power factor changes with the output power of the
inverter.
Select Q(P) mode and
Press
to enter into the
“Run-para-Q(P)” sub-menu.
Press
to move the cursor;
Press
to enter the
editing mode, then the selected parameter will be
shaded.
Press
to increase one-step value;
Press
to
decrease one-step value.
Press
ENTER
to confirm the setting and exit from the
editing mode.
Tab. 10-8
Italy “Q(P)” Mode Parameters Explanation
Parameter
Explanation
Default
Range
Step
PA*
Active power at point A (in %)
20% 20~100%
1%
PB*
Active power at point B (in %)
50% 20~100%
1%
PC*
Active power at point C (in %)
100% 20~100%
1%
Pf max
Power factor at point C
0.9
0.9~1
0.01
Uin**
Enter Q(P) regulation mode
when grid voltage is above
Uin
105% 100~110%
1%
Uout**
Exit from the Q(P) regulation
mode when grid voltage is
below Uout
100% 90~100%
1%
*PA < PB
≤
PC ** Uin
>
Uout
Содержание SG60KTL
Страница 1: ...SG60KTL V142 UEN Ver11 201712 Version 1 1 User Manual SG60KTL PV Grid connected Inverter ...
Страница 2: ......
Страница 5: ...III Symbols on the Inverter Body ...
Страница 10: ......
Страница 23: ...User Manual 2 Product Description 13 P Vmin 266V Pn Vgrid 230V Fig 2 6 Grid under voltage derating ...
Страница 71: ...User Manual 10 Operation of LCD Display 61 10 2 Menu Tree Fig 10 1 Menu tree ...