6 Electrical Connection
User Manual
32
Step 1
Disconnect the AC circuit breaker and ensure it will not reconnect accidentally.
Step 2
Unscrew the 6 bolts on the front cover of the lower
junction box.
Step 3
Peal the cables as shown below.
The AC cables must be Hard-line.
Customer can choose to connect the neutral cable or not, it’s not
mandatory to connect the neutral cable to the inverter.
The cross-section of the AC cable must be selected carefully in order to prevent
accidentally disconnections of the inverter from the grid due to high impedance of
the cable.
No.
Description
Remark
A*
Protective layer
External diameter of the cable: 30.5-50 mm
B
Length of insulation to be
stripped off
24 mm
C Insulation
layer
-
D
Cross section of AC cables
Range: 25-150mm
2
; recommended value: 50
mm
2
* The external diameter of the AC cable described in A is proper range.
If you select AC cable with the external diameter within the range of 30.5-40 mm,
please select the smaller AC cable gland.
If you select AC cable with the external diameter within the range of 40-50 mm,
please select the larger AC cable gland.
The following table gives the recommended max. length of the AC cables based on
the cross-section of the AC cables.
Содержание SG60KTL
Страница 1: ...SG60KTL V142 UEN Ver11 201712 Version 1 1 User Manual SG60KTL PV Grid connected Inverter ...
Страница 2: ......
Страница 5: ...III Symbols on the Inverter Body ...
Страница 10: ......
Страница 23: ...User Manual 2 Product Description 13 P Vmin 266V Pn Vgrid 230V Fig 2 6 Grid under voltage derating ...
Страница 71: ...User Manual 10 Operation of LCD Display 61 10 2 Menu Tree Fig 10 1 Menu tree ...