10 Operation of LCD Display
User Manual
72
Parameter
Description
Default
Range
Time
param
Standby time
Time from inverter
standby to startup
20s 20~255s
Recover time
Time from inverter fault
is removed to standby
30s
[IT: 300s]
0-900s
Derating param
Set the Derating param
to OFF or ON. If it is ON,
inverter will operate
with power derating
when grid frequency
exceeds the set value.
[OFF] [OFF]/
[ON]
Iso
param
ISO
Set the ISO protection
function to ON or OFF.
When it is ON, inverter
will not connect to the
grid when resistance to
the ground is below the
set value.
[ON] [OFF]/
[ON]
ISO pro value
Set the resistance to
the ground.
30
K
Ω
20~3000
K
Ω
LVRT param
Set the LVRT to OFF or
ON. When it is ON,
inverter can keep
grid-connection for a
certain time when grid
fault occurs and
provide reactive power
for grid recovery.
- [OFF]/
[ON]
HVRT param
Set the HVRT to OFF or
ON. When it is ON,
inverter can keep
grid-connection for a
certain time when grid
fault occurs and
provide reactive power
for grid recovery.
[OFF] [OFF]/
[ON]
10.10.2 Active/Reactive Power Parameters
Main Screen
(Press
ENTER
)
→
Menu
(Press
×
3)
→
Set-param
(Press
ENTER
)
→
Enter
password
(Press
ENTER
, Press
)
→
Run-param
(Press
ENTER
)
→
P-Q Param (Press
ENTER
)
Содержание SG60KTL
Страница 1: ...SG60KTL V142 UEN Ver11 201712 Version 1 1 User Manual SG60KTL PV Grid connected Inverter ...
Страница 2: ......
Страница 5: ...III Symbols on the Inverter Body ...
Страница 10: ......
Страница 23: ...User Manual 2 Product Description 13 P Vmin 266V Pn Vgrid 230V Fig 2 6 Grid under voltage derating ...
Страница 71: ...User Manual 10 Operation of LCD Display 61 10 2 Menu Tree Fig 10 1 Menu tree ...