10 Operation of LCD Display
User Manual
70
Press
to move the cursor
and press
to change
value. Press
ENTER
to confirm setting.
The positive symbol “+” can be changed to the
negative symbol “-”.
The adjustment range is from -9999 to +9999 kWh.
(Energy-adj value)= (Real measured value) - (E-tot
reading value).
10.9.4 Load Default
All history information will be unrecoverable cleared and all parameters will
return to the default value except the protective parameters and time once
the “load default” operation is performed.
Main Screen (Press
ENTER
)
→
Menu (Press
×
3)
→
Set-param(Press
ENTER
)
→
Enter
password (Press
ENTER
)
→
Sys-param(Press
ENTER
, Press
×3)
→
Load default (Press
ENTER
)
Press
ENTER
to confirm “load default”.
10.9.5 Checking Firmware Version
Main Screen (Press
ENTER
)
→
Menu (Press
×
3)
→
Set-param(Press
ENTER
)
→
Enter
password (Press
ENTER
)
→
Sys-param(Press
ENTER
, Press
×4)
→
Firmware
version(Press
ENTER
)
Inverter shows detailed firmware information,
including LCD version and DSP version.
The firmware version information is read only.