STULZUltraSonic-SystemforDirectRoomHumidificationBNB-
Installation
7.3.
Wall-mounted installation
Select the right type of installation to suit local circumstances. The examples below show the installation
ofaBNBultrasonichumidifieronabracketandinatray.Iftheultrasonichumidifierismountedonawall
bracket,thesafetyoverflowmustbeconnectedtothedrainviaahose.Ifitisnotpossibletoconnectthe
safetyoverflowtothedrain,theultrasonichumidifiercanbeinstalledinatrayinwhichawatersensor
isfitted.Installtheunitsuchthatthemistexpelledbythefanisdistributeduniformlyeverywhereinthe
room.(Alsoseesection
"5. Design and planning" on page 26
).Persons in the blow-out area of the
humidifiermustmaintainadistanceofapprox.5.0m.Boththewallbracketandsafetytrayareavailable
fromSTULZasoptionalaccessories(seesection
"3.1. Optional accessories" on page 13
).
CAUTION
Installation in an elevated location.
Ifinstallingthehumidifierinanelevatedlocation,makesurethatitiseasilyaccessibleforadjustments,
inspections,maintenanceandrepairwork.Insufficientspacecancausemaintenancepersonnelto
suffer injuries and accidents!
CAUTION
Bear local conditions in mind.
Adaptthe(on-site)fasteningoftheunitinlinewithlocalconditions.
CAUTION
Horizontal position.
The unit must be mounted precisely horizontally.
●
Itisessentialtocheckthepositionofthehumidifierbeforestartingitup!
NOTICE
CAUTION
Adhere to set clearances.
Between the mist guide tube and any component that may be located in front of the unit, leave a clear-
ancethatisgreaterthanthehumidifierdistance.
●
See section "5.1.Humidifierdistance"onpage27.
NOTICE
CAUTION
Installation clearance.
Leaveminimumclearanceof500mmbetweentheupperedgeoftheultrasonichumidifier
and the ceiling.
●
See section "7.2. Installation clearances" on page 36.
NOTICE
CAUTION
Load-bearing wall.
Thewallmustbeabletobeartheweightofthehumidifier.
NOTICE
CAUTION
Direct exposure to air from air conditioning units.
Avoiddirectlyexposingthehumidifieroutlettoairfromairconditioningunits.
NOTICE