STULZUltraSonic-SystemforDirectRoomHumidificationBNB-
Maintenance
7
Clean mist outlets with demineralized
drinking water.
Take care not to damage the wiper ring.
9
Assemble the unit in reverse order.
6
Remove any mineral residues using
a citric acid-based domestic cleaning
agent and soft cloth.
The installation posi-
tion of the wiper rings
isindicatedby▼.
CAUTION
Trapped cables.
During installation, take care not to trap any
cables between parts of the housing!
Note
CAUTION
Flush water pipes.
Flush the water pipes with the highest possible
pressure before connecting units to the water
mains.
Note
8
Disinfectthewatertank:
a)Brushorsprayallpartswith5%
hydrogenperoxidesolution(H
2
O
2
)
a minimum of three times at 15-
minute intervals.
b)Afteranexposuretimeofapprox.
30 min, rinse parts thoroughly several
times with water.
c)Flushwaterpipeswiththehighest
possible pressure before connecting
units to the water mains.
CAUTION
Risk of chemical burns.
Use safety goggles when handling cleaning
agents or hydrogen peroxide solution. These
preparations are "caustic"!
CAUTION
Microbial contamination.
If microbial contamination is evident, disinfect
the tank at shorter intervals.