Installation
STULZUltraSonic-SystemforDirectRoomHumidificationBNB-
7.4.
Connecting water supply line(s)
CAUTION
Frost protection.
Protect the entire system from frost.
NOTICE
CAUTION
Contaminated water pipes.
Filings and dirt must not get into water pipes!
●
All pipes must be cleaned before they are connected to the unit.
NOTICE
CAUTION
Resistant materials.
Theconnectionbetweenthedemineralizationsystemandthehumidifiermustconsistofamaterialthat
is resistant to demineralized water.
●
Only use approved materials. See "4.7. Application limits" on page 20.
NOTICE
CAUTION
Regulations from water supply companies.
Regulations from water supply companies must be complied with.
WARNING
Fortheultrasonichumidifier,usedemineralizeddrinkingwaterwiththeconductivitythatissuitablefor
yourapplication(seesection"4.7. Application limits" on page 20).
Provide each unit with a stop cock in the drinking water supply pipe.
Cleanalllinesbeforeconnectingthemtothehumidifier.Thesupplylinecanbeapressurehoseora
stainless steel tube, depending on the safety risk.
Connecttheoverflowpipeforadditionalsecurity.However,nowaterflowsintotheoverflowduringnor-
mal operation.
CAUTION
Demineralized drinking water.
Theultrasonichumidifierisoperatedwithdemineralizeddrinkingwater,toensurethatthetransducers
retain their function throughout the unit's service life. Furthermore, if the mineral content of the water is
too high for the planned application, this may lead to the formation of deposits in the humidified room.
●
Check the mineral content and conductivity of the drinking water to prevent damage to property.
●
Replenish ion exchangers regularly and in good time.