STULZUltraSonic-SystemforDirectRoomHumidificationBNB-
Designandplanning
CAUTION
Reducing conductivity.
Depending on the planned application, it may make sense to further reduce conductivity.
This must be done by the plant operator.
Note
1
1
1
1
2
2
4
2
2
3
3
3
3
5
5
6
6
7
7
7
7
6
6
5
5
4
4
5.2.
Applications
The type of water treatment may differ depending on the application.
5.2.1. Comfort applications
●
Offices,doctors'surgeries,productionplants,storagefacilities
●
Recommendedwaterquality:~20μS/cm
●
Recommended water treatment using reverse osmosis, with downstream ion exchanger where
necessary.
Reverse osmosis
Storage tank
Open-loop/closed loop control
(ionexchangerifnecessary)
Conductivity monitor
Conductivity sensor
BNB
5.2.2. Equipment room applications
●
Equipmentrooms,serverrooms,laboratories,applicationswithlargecirculatingflowsofairandalow
proportionoffreshair(e.g.80/20)
●
Recommendedwaterquality:<5μS/cm
●
Recommended water treatment using reverse osmosis, downstream ion exchanger essential
Reverse osmosis
Storage tank
Open-loop/closed loop control
Ion exchanger
Conductivity monitor
Conductivity sensor
BNB