background image

1

04/06/04  LIT-H200X-E02 H200.doc

ELECTRONIC HUMIDISTAT: H200

  ONE OR TWO STAGES

DESCRIPTION                                                               

The H200 series low voltage, microcomputer-based PI
(proportional and integral) humidistats are designed for
accurate humidification and/or dehumidification control
in non-corrosive commercial applications such as:
hospitals, schools, office buildings, retail stores,
museums, computer rooms, etc.

The H200 series is available with one or two outputs
for maximum flexibility.  Outputs can be of the following
type: proportional, on/off, and pulse width modulation
(PWM).  In addition, a wide variety of mounting
configurations is available.  Sensing options include
remote duct and room as well as integral room and
duct.

Setpoint adjustment can be either concealed or
exposed, adding even more versatility to the product.
Exposed models feature internally selectable minimum
and maximum setpoint knob stops.

In order to facilitate periodic recalibration, the H200
series contains a unique autocal key, which permits
instant recalibration (see dimension drawing on page 5
for location).

Each humidistat is computer calibrated and factory
programmed with default parameters. All control
parameters (such as proportional band, stage
differential, etc.) may be changed in the field with the
H263 programming tool without having to remove the
thermostat cover.  The H263 also doubles as a
diagnostic tool and indicates the status of all the inputs
and outputs, and will reduce troubleshooting time by
quickly identifying the specific problem.

Fig.1: Wall mounted humidistat

Features

Benefits

 Microcomputer-based design with PI algorithm

Exceptional accuracy

 One or two outputs

Controls humidification and dehumidification equipment

 On/off and/or proportional outputs

Greater flexibility

 Direct or reverse acting outputs

Controls humidification and dehumidification equipment

 Integrated and remote sensing

Larger choice of mounting options

 Autocal button

Permits instant recalibration

 Concealed or exposed set point

Can be used in a large variety of environments

 Ouput signal to digital indicating devices

Increases functionality of product

 Optional H263 diagnostic tool with digital display

Simplifies troubleshooting

 Sensor failure protection

Prevent water dammage

 CE approved

Can be sold in European markets

Содержание Micro-stat H200 Series

Страница 1: ...page 5 for location Each humidistat is computer calibrated and factory programmed with default parameters All control parameters such as proportional band stage differential etc may be changed in the field with the H263 programming tool without having to remove the thermostat cover The H263 also doubles as a diagnostic tool and indicates the status of all the inputs and outputs and will reduce tro...

Страница 2: ...y output and one relay dehumidify output Humidistat and sensor are duct mount Setpoint is user adjustable Resolution 0 5 for retransmit only See sensor specifications for dimensions of sensors Note the complete order code includes the sensor that will be shipped with the humidistat WIRING 2 ON OFF OUTPUTS Single transformer Fig 2 Wiring diagram with single transformer Multiple transformers Fig 3 W...

Страница 3: ...o output 2 The humidity sensor is located in the return air duct Humidistat model number H200 69 13 10 Fig 6 Application example 6 COMMON N A INPUT MAIN SENSOR N A 10 Vdc 9 10 8 7 OUTPUT 1 TRANSMITTER 0 to 10 Vdc 0 to 5 Vdc OUTPUT 2 24 Vac 0 to 10 Vdc 4 5 3 24 Vac 2 1 FOR CONTROL HUMIDITY SENSOR RED BLACK WHITE DDC SYSTEM ELECTRONIC MOTOR or SCR or METER 6 COMMON N A N A INPUT MAIN SENSOR 10 Vdc 9...

Страница 4: ...uct mounted humidistat This humidity sensor can be mounted directly onto the supply or return of the ventilation duct The H200 may be located on the wall with humidity sensing from the remote H71 sensor location H80 REMOTE WALL SENSOR H263 PROGRAMMING TOOL This humidity sensor can be wall mounted in any remote location The humidistat may be located on the duct or other location with humidity sensi...

Страница 5: ...ol Code t1 0 On off 1 8 minutes 2 1 second Time 1 Time period for output no 1 t2 0 On off 1 8 minutes 2 1 second Time 2 Time period for output no 2 rA 0 C 1 F 1 DO NOT CHANGE Range Temperature Scale Ca 13 Calibration deviation mode DO NOT MODIFY USE AUTOCAL PROCEDURE FOR H100 TRANSMITTER USE THE ZERO POTENTIOMETER ON THE TRANSMITTER hA 0 à 127 Hardware assembly Code related to thermostat model and...

Страница 6: ... 5 C to 50 C 32 F to 122 F Control 0 to 95 R H non condensing Sensor 0 to 100 R H see Note 1 Resolution 0 1 Repeatability 0 5 Accuracy and sensor interchangeability 2 R H from 0 to 100 R H Range 10 to 90 R H for 5 to 50 C 41 F to 122 F Temperature effect 0 05 F Outputs Isolated Triac 30 Vac at A max 0 to 5 VDC into 1KΩ resistance min 0 to 10 VDC into 2KΩ resistance min 0 5 VDC at 20 mA max for bot...

Отзывы: