79
08/13424999756
Compact control panel 4A, 4A/M und 8A, 8A/M
Technical data
The power supplies and electrical control equipment are to be operated exclusively with the components authorised by
the manufacturer.
Electrical properties
Power supply means
ELV:
class
A
Primary
energy
:
mains
Secondary
energy: battery
maximum interruption time
between energy sources:
< 1 ms
Primary energy supply
Operating voltage supply:
230 V AC / 50 Hz, (±10 %), separately fused
System voltage:
27 V DC (nominal) (-25 % / +10 %)
Power consumption:
approx. 150 W by current supply 4 amps,
approx. 300 W by current supply 8 amps
Current consumption mains:
max. 0.8 amp by current supply 4 A,
max. 1.6 amp by current supply 8 A
Power consumption (Standby):
< 5 W
Monitoring:
yes, detection failure of the 230 V AC mains supply
Terminal:
screw terminals max. 2.5 mm2
Fuse:
mains 230 V AC: T 3.15 A/H
motor circuit: FKS 5A / FKS 10A
Secondary energy supply
Batteries:
type 4A: 2.2 Ah, type 8A: 7.2 Ah,
2 x 12 V with total discharge prot. in case of low
voltage, monitor funct. for wire breakage and fuse failure,
service
life
4
years
Batterie type:
lead gel battery witk VdS Zertification
Emergency power:
72 h, approx. by use as magnetic clamp control panel
approx. 7 h by 80 mA current consumption
Stand-by current:
17,0 mA according to DIN EN 12101-10
Power output after 72 h in
Emergency operation:
type 4A: 4A, type 8A: 8A for 180 sec. according to DIN EN 12101-10
maximum current output
type 4A: 4A, type 8A: 8A (switched off at the primary energy source)
Charging time:
20 h for emergency power
Terminal:
2 pole, max 2.5 mm2²
Monitoring:
yes,
cyclic
Fuse:
FKS
10A
Output
Voltage:
27 V DC (nominal) (-25 % / +10 %)
power:
type 4A: Pmax = 108W; Pmin = 0W; type 8A: Pmax = 216W; Pmin = 0W
Ripple:
Drives: Vpp < 1 %
Magnetic
clamps:
Vpp
<1
%
Power
(nominal):
drives:
type 4A: 4 amp at 30 % ON* / type 8A: 8 amp at 30 % ON*
output
separately
fused,
magnetic
clamp:
type 4A: 1 amp at 100 % ON* / type 8A: 2 amp at 100% ON*
*
Referring
to
10
minutes
Opening / closing sequence:
reversal of voltage polarity
Pause time during change of
approx. 300 ms (can be changed via service port
polarity:
software)
Timing in accordance with
yes, alteration of direction of travel every 2 minutes,
prEN 12 101-9:
during the first 30 min after SHE activation (to ensure
opening if dome lights and skylights etc. are iced-up)
Automatic activation:
Open/Close direction: after 3 min* (at ventilation operation)
Cable monitoring function:
via third monitoring circuit in con junction with monitoring diodes
Terminal:
max. 6 mm², screw terminal
Drives / Magnetic clamps:
in accordance with max. current draw of the drives / magnetic clamps
Fuse:
FKS
10A